XGTD5-(12,24)40.5 Indoor Gas Insulation Metal-Clad High Voltage Switchgear

 

 

General introduction

(XGTD5)-(12/24)40.5 series indoor gas-insulated metal-clad switchgear (hereinafter called "C-GIS panel") is a switchgear which uses a spring-operated vacuum circuit breaker, electrically operated three station isolation / grounding switch, transformer, lightning arrester as the main components, and completely seals all HV conductors in the metal-clad enclosure with SF6 gas as the insulating medium.

The product has features of flexible combinations, great safety, complete interlocking logic as well as extendibility, miniaturization and free for maintenance. So that it was commonly used in infrastructure construction for power station, power substation, movable transformer pack, rail traffic, buildings that have the 35kV or below nominal voltage. Especially for some sever environment like high altitude, heavy pollution and high humidity.

The product quality assurance is based on researching, developing designing and producing required by quality system and continues to improve. So it is completely complying with the newest version or revised version of following standard, but not limited to them.

 

Main technical parameters of switchgear

ItemUnitParameters
Rated voltagekV122440.5
Rated currentA630/1250/1600/2500
Rated frequencyHz50/60
1 min rated power frequency withstand voltage (RMS)

Phase to Phase

Phase to earth

kV426595
Insulation Distance4879118
Rated Lightning impulse withstand voltage (peak)

Phase to Phase

Phase to earth

kV75125185
Insulation Distance85145215
Rated power frequency withstand voltage of auxiliary circuitkV2
Rated short-circuit breaking current (RMS)kA20/25/31.5/40
Rated short-circuit making current (peak)kA50/63/80/100
Rated short-time withstand current (4s)kA20/25/31.540
Rated peak withstand currentkA50/63/80/100
Main circuit resistance of each phaseμΩ

Rated current≤1600A, Rc≤220

Rated current≥2000,Rc≤105

Rated voltage of auxiliary and control circuitVDC110/220 AC220
Rated SF6 gas pressure (20℃)MPa/
Min SF6 gas pressure (20℃)MPa/
Annual SF6 gas loss rate≤5
Degree of Protection/

HV compartment IP67

LV compartment IP4X

WeightKg

1000~1600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

                                                  Type and designation

 

                              Hoisting diagram

Hot Products

XGTD5-(12,24)40.5 Indoor Gas Insulation Metal-Clad High Voltage Switchgear General introduction ...
XGTD5-(12,24)40.5 Indoor Gas Insulation Metal-Clad High Voltage Switchgear Service conditions a. ...
XGTD5-(12,24)40.5 Indoor Gas Insulation Metal-Clad High Voltage Switchgear Service conditions a. ...
220kV Three Phase Power Transformer Oil Immersed type IEC60076 The 220kV transformer adopted the ...
1. General introduction XGTD8-12 indoor environmental gas insulated metal-clad switchgear ...
S11 series full sealed 20KV three phase distribution transformer 1. General of S11 series full ...