XGTD5-(12,24)40.5 Indoor Gas Insulation Metal-Clad High Voltage Switchgear
General introduction
(XGTD5)-(12/24)40.5 series indoor gas-insulated metal-clad switchgear (hereinafter called "C-GIS panel") is a switchgear which uses a spring-operated vacuum circuit breaker, electrically operated three station isolation / grounding switch, transformer, lightning arrester as the main components, and completely seals all HV conductors in the metal-clad enclosure with SF6 gas as the insulating medium.
The product has features of flexible combinations, great safety, complete interlocking logic as well as extendibility, miniaturization and free for maintenance. So that it was commonly used in infrastructure construction for power station, power substation, movable transformer pack, rail traffic, buildings that have the 35kV or below nominal voltage. Especially for some sever environment like high altitude, heavy pollution and high humidity.
The product quality assurance is based on researching, developing designing and producing required by quality system and continues to improve. So it is completely complying with the newest version or revised version of following standard, but not limited to them.
Main technical parameters of switchgear
Item | Unit | Parameters | |||
Rated voltage | kV | 12 | 24 | 40.5 | |
Rated current | A | 630/1250/1600/2500 | |||
Rated frequency | Hz | 50/60 | |||
1 min rated power frequency withstand voltage (RMS) | Phase to Phase Phase to earth | kV | 42 | 65 | 95 |
Insulation Distance | 48 | 79 | 118 | ||
Rated Lightning impulse withstand voltage (peak) | Phase to Phase Phase to earth | kV | 75 | 125 | 185 |
Insulation Distance | 85 | 145 | 215 | ||
Rated power frequency withstand voltage of auxiliary circuit | kV | 2 | |||
Rated short-circuit breaking current (RMS) | kA | 20/25/31.5/40 | |||
Rated short-circuit making current (peak) | kA | 50/63/80/100 | |||
Rated short-time withstand current (4s) | kA | 20/25/31.540 | |||
Rated peak withstand current | kA | 50/63/80/100 | |||
Main circuit resistance of each phase | μΩ | Rated current≤1600A, Rc≤220 Rated current≥2000,Rc≤105 | |||
Rated voltage of auxiliary and control circuit | V | DC110/220 AC220 | |||
Rated SF6 gas pressure (20℃) | MPa | / | |||
Min SF6 gas pressure (20℃) | MPa | / | |||
Annual SF6 gas loss rate | ‰ | ≤5 | |||
Degree of Protection | / | HV compartment IP67 LV compartment IP4X | |||
Weight | Kg | 1000~1600 |