Home Companies Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA

Ningbo Tian'an Jinghua Power Technology Co., Ltd.
Active Member

Contact Us

[China] country

Address: 21/F, Building 1, No. 816,Jinghua Road, Hi-tech Zone,Ningbo, Zhejiang, P.R. China

Contact name:Tony ma

Inquir Now

Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA

Country/Region china
City & Province ningbo zhejiang
Categories Battery Chargers
InquireNow

Product Details

Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA
 
Product Description

General
GW7B isolating switch is a kind of outdoor HV electricity transmission equipments at three-phase AC frequency of 50/60Hz. It is used for breaking or connecting HV lines under no loads so that these lines can be changed and connected and the way the electricity runs is changed. In addition, it can be used to exercise safe electrical insulation for such HV electric apparatuses as bus and breaker. The switch can open and close inductance/ capacitance current and is able to open the bus to switch current.
This product has three posts with horizontal open breaks. JW10 grounding switches may be attached to the product at one or two sides. 72.5~252kV isoalting siwtch adopts CJ2 or SRCJ2 manual actuator to realize the tri-ole linkage. The grounding switch adopts CS11 or SRCS manual actuator to actualize tri-pole linkage. 363kV isoalting switch adopts SRCJ2 motor's actuator to realize the single pole operation; while the grounding switch takes SRCS manual actuator or SRCJ2 motor's actuator to realize the single pole operation and also tri-pole linkage.


Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA Technical data

S/NItemUnitParameter
1Rated voltagekV72.5145252363420
2Rated insulation level      
3Rated power frequency withstand voltage (1 min)      
4To earthkV160275460210520
5Across open breakskV200275+85460+145210+210610
6Rated lightning impulse withstand voltage      
7To earthkV350650105011751425
8Across open breakskV410650+1201050+2001175+2951425+240
9Rated switch impulse withstand voltage (peak)      
10between phase/ to earthkV------1425/9501574/1050
11Across open breakskV------850+295900+345
12Rated frequencyHz50/6050/6050/6050/6050/60
13Rated currentA1250
2000
2500
3150
4000
1250/20002000
2500
3150
4000
5000
31,505,0003150
14Rated short-time withstand currentkA
40
50
31.5/4050/63160160
15Rated peak withstand currentkA
100
125
80/100125/1606363
16Rated duration of short circuits44332
17Rated terminal mechanical load      
18Horizontal -logntitudinalN750/10001250150025002000
19Horizontal- verticalN500/75075010002000660
20Vertical forceN7501000125015001500
21Isolating switch bus capacity of switching
currents and opening/ closing
 100V, 1600A,
100 times
100V, 1600A,
100 times
300V, 1600A,
100 times

450V, 3200A, 3times
400V, 1600A,
100 times
300V, 1600A,
100 times
22Grounding switch induction current open/ closing capacity     
23Electromagnetic induction-typ current (current/ voltage)A/kV100/4 (80/2)100/6 (80/2)160/15 (80/3)1250/35 (160/10)160/10 (80/2)
24electrostatic induction current (current/ voltage)A/kV2/65/6 (2/6)10/15 (3/12)50/50 (18/17)18/20 (1.25/5)
25Times of opening and closingtimes1010101010
26isolating switch small current open/ closing capacity     
27capacitive currentA--1111
28Inductive currentA--0.50.50.50.5
29RIV radio interference voltageuV<500<500<500<500<500
30Creepage distancemm>1813
2248
>3625
4495
>6300
7812
>9450>10500
31Mechnical endurancetimes500050001000500010000
32Applicable altitudes <2000<2000<2000<3000<1000
33Motor operating mechanism      
34Model CJ2CJ2SRCJ2SRCJ2SRCJ2
35Motor voltageVAC 380
DC220
AC 380
DC220
AC 380
DC220
AC 380
DC220
AC 380
DC220
36Control circuit's voltageV
AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110
37Opening time and closing times7+17+116+116+116+1
38Output shaft rotation 180180180180180
39Manual operating mechanism      
40Model CS11CS11SRCSSRCSSRCS
41control circuit voltageVAC 220AC 220AC 220AC 220AC 220

 
 Purpose
High voltage disconnectors are divided into indoor type and outdoor type. The outdoor type includes single pole switch and three pole disconnector, which is often used as the first circuit breaker isolating switch to separate the power supply line from the user; the indoor type is often connected in series with the high-voltage circuit breaker to ensure the reliability of power failure. In addition, in the high-voltage complete set of power distribution equipment, the disconnector is commonly used as voltage transformer, lightning arrester, transformer used in power distribution station and high-voltage control appliance of metering cabinet. 

 

Hot Products

420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect 420kV 5000A HV ...
Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA Product Description General GW7B ...
GW4-126D outdoor HV AC disconnecting switch 1. Product Introduction GW4-126D outdoor HV AC ...
Voltage Regulator Oil Immersed Power Transformer ONAF 110KV SZ 110kV Oil-immersed type power ...
Power Line Electrical 220kV Oil Immersed Power Transformer GB1094 IEC Electrical 220kV Two-winding ...
110kV Outdoor Three Phase Shift 8kW Oil Immersed Power Transformer Full Sealed 110kV Three-phase ...