Home Companies Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Metal Clad 40.5KV KYN61 High Voltage Switchgear 25kA Draw Out

Ningbo Tian'an Jinghua Power Technology Co., Ltd.
Active Member

Contact Us

[China] country

Address: 21/F, Building 1, No. 816,Jinghua Road, Hi-tech Zone,Ningbo, Zhejiang, P.R. China

Contact name:Tony ma

Inquir Now

Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Metal Clad 40.5KV KYN61 High Voltage Switchgear 25kA Draw Out

Country/Region china
City & Province ningbo zhejiang
InquireNow

Product Details

KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

1. General Of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

KYN61-40.5 Air Insulated Metal-clad Switchgear is suitable for application at three phases, 50Hz, 40.5kV power distribution system. This product has functions of protection, control and monitoring.

 

2. Service condition of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

a. Ambient temperature: +40 to -15℃

b. Elevation: no more than 10000m

c. Humidity:

Daily average relative humidity shall be not higher than 95%

Monthly average relative humidity shall be not higher than 90%

d. Earthquake: no more than 8 degree

Ambient air should be free of the obvious pollution of aggressive or flammable gases, or vapor, etc.

The usage of the product beyond of the environment for demanded technical conditions should be after the negotiation between the client and factory.

 

3. Type designation of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

4. Technical parameters and requirement of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

No.ItemUnitParameter
1Rated voltagekV40.5
Rated frequencyHz50
3Rated main busbar currentA1250, 1600, 2000
4Rated branch busbar currentA1250, 1600, 2000
5Rated insulation level1min power frequency withstand voltagekVPhase to phase, Phase to earthPrimary Insulation Distance
95115
Lightning impulse withstand voltage185215
1min power frequency withstand voltage of Auxiliary control circuitV2000
6Rated short circuit breaking current (effective value)kA25, 31.5
7Rated making current(peak time)kA63, 80
8Rated short time peak withstand currentkA63, 80
94 s’ short time withstand currentkA25, 31.5
10Rated voltage of auxiliary control circuitV≈110, ≈220
11Protection level Enclosure IP4X, Chamber IP2X
12Overall sizemm1200 or 1400x2800x2600

 

 

Hot Products

HXGT10-40.5 Indoor Gas Insulation Metal-Clad Switchgear / Gas insulated switchgear Product ...
KYN61-40.5 High Voltage Distribution Board With Metal Clad Production of KYN61-40.5 High Voltage ...
GIS 40.5KV Metal Mounted Type Distribution High Voltage Switchgear Features of GIS 40.5KV Metal ...
KYN61-40.5 Drawable Switchgear Power distribution Description of KYN61-40.5 Drawable Switchgear ...
KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear 1. General Of KYT1 (KYN61)-40.5 Metal-clad Draw...
Hight voltage Switch cabinet XGN65 (HXGT10)-40.5 type SF6 Ring Main Unit Main purpose and applicatio...