DC 252kv 125KA HV Disconnect Switch Loop Overheating Loop Overheating

 

General overview

GW23 (GT9) 252D/2500-50 Type Double Column Outdoor AC HV Disconnector is developed on the basis of aiming at existing defects about disconnector conducting loop overheating, operating mechanism failure, metal material corrosion serious, and then making great improvement.

 

DC 252kv 125KA HV Disconnect Switch Loop Overheating Loop Overheating Characteristic:
1. Application of friction type contacting structure in main knife moving conductive contact surface
2. Auto-locking device of breaking and closing positions effectively prevents the separation of dynamic/static contacts due to wind or electric motive force
3. The application of non-oil bearing and copper alloy sleeve on rotating point making it have auto-lubrication function and conquers the corrosion and seizure of the rotating point
4. Application of advanced surface processing technique and anti-rust aluminum, stainless steel greatly enhances surface anti-rust property
5. Three-pole linkage and electric/manual operation of main switch
6. Fitted with earthing switch that has the same short-circuit current withstand capability as disconnector
7. Effective prevention of mal-operation by electric/mechanical dual interlock between disconnector and earthing switch

 

DC 252kv 125KA HV Disconnect Switch Loop Overheating Loop Overheating Technical parameters

 

S/NNameUnitParameters
1Rated voltagekV252
2Rated currentA2500
3Peak withstand current of disconnector and earthing switch (peak)kA125
43s short-time withstand current of disconnector and earthing switch (r.m.s)kA50
5Main circuit resistance of disconnectorμΩ≤130
61min power frequency withstand voltage(r.m.s)Phase-to earth(dry, wet)kV395
Fracture460
7Lightning impulse withstand voltage (1.2/50μs)Phase-to earthkV950
Fracture1050
8Mechanical endurance test of disconnector and earthing switchTimes2000 for each

 

Hot Products

Fused Outdoor 12kv 3000m Sea Level HV Disconnect Switch 50hz Fused Outdoor 12kv 3000m Sea Level HV ...
35KV 3 Phase 630A 3000M Altitude 4S Outdoor Disconnect Switch Main Characteristics of 35KV 3 Phase ...
Electrical Anti Electrodynamic Space Saving GT10 HV Disconnect Switch 1250A Electrical Anti ...
Single Pole Fused Disconnect Switch Electricity Isolation Overview GW22 (GT8)-126D/1600-31.5 ...
DC 252kv 125KA HV Disconnect Switch Loop Overheating Loop Overheating General overview GW23 (GT9) ...
AC 145kv High Voltage Disconnect Switch 1000m GW4 No Load Change These disconnectors are , no load ...