Data Center UPS Modular UPS Rack Mounted 10-90KVA

Country/Region china
City & Province shanghai guangxi
Categories Uninterrupted Power Supply (UPS)
InquireNow

Product Details

Product Application
 

TCRM series modular UPS power, the industry leading, all-digital power distribution product, collects the most advanced technology in power electronics and automatic control, thus resulting in breakthrough improvements in power reliability, availability and maintainability of the critical equipment.
 

It integrates the technical features of traditional tower-type with the need of modern modular server rooms, ensuring modular design together with high reliability of the system.
 

 

Range of Power / Working Methods
 

10-90kVA, 3 in 3 out, 3 in single out, 1 in-1 out (TCRM020/10X, TCRM040/10X, TCRM060/10X), online double conversion
 

 

Product Features

 

  • Smart Protection Solutions
     

TCRM series modular UPS power distribution has both software and hardware in the power modules and has its system under protection. When possible problems of voltage, current, thermal performance and short circuits occur, rapid and efficient protection can be provided so as to ensure the whole system's security and reliability.
 

  • Full Digital Control
     

With 32-bit high-speed DSP digital control, the communication system introduces the most advanced CAN-BUS technology, making its performance more stable and safer.
 

  • Core Power Devices with an Integrated Packaging Structure of IGBT Modules
     

TCRM series modular UPS features an integrated packaging of IGBT modules, greatly improving the reliability of core devices. It avoids the uneven flow and voltage stress caused by the discrete IGBT parallel approach, and its unique isolation duct design significantly improves its adaptability to the environment.
 

  • Smart Battery Management Solutions
     

Each power module has a separate, digital high-power charger built in, provision of 20% power capacity for charging. Charge and discharge circuits are in DSP digital control, for excellent battery management and extended battery life.

 

 

  • Green Energy Conservation
     

Input power factor is more than 0.99, input harmonics less than 3%, and overall efficiency up to 95% or more; and its smart sleep function effectively improves the efficiency of the entire UPS.
 

  • Powerful Remote Network Management Solutions
     

SNMP network management card allows for remote monitoring and control of the UPS system via the network, and for simultaneous remote monitoring of multiple devices via the matching remote control box.
 

  • "Zero Threshold" of Maintenance
     

It is maintained just in minutes, and adopts autonomous identification of module IDs without need to manually set the program. Critical waveform recording makes it convenient for fault analysis.
 

  • Battery Cold Start
     

The system comes with a cold start with batteries to power on (for 20 kVA/25 kVA/30 kVA/45 kVA/50 kVA power module).
 

  • Hot-Swapping Static Bypass Monitoring Module
     

Monitoring and static bypass modules are hot-swappable, with each power module auto-controlled and auto operated to avoid single point failure.

 

 

 

Technical Specifications
 
ModelTCRM
020/10X
TCRM
040/10X
TCRM
060/10X
TCRM
030/15X
TCRM
045/15X
TCRM
090/15X
Capacity20kVA40kVA60kVA30kVA45kVA90kVA
Main InputTerminal Connectionthree phase + N + PE
Input Voltage380/400/415VAC (Line-Line) 220/230/240VAC (phase voltage)
Input Frequency50/60Hz
Power Factor>0.99
Current Distortion RateTHDi<4%
Range of Voltage304-478Vac (Line-Line) at full load; 304V-228Vac (Line-Line) linear derating from 100% to 75%
Frequency of Voltage40-70Hz
BatteryVoltage of Battery±240VDC (32-44 cells adjustable)
Charging Power20%* Active power
Charging Voltage Accuracy±1%
BypassVoltage of Bypass380V/400V/415V (Line-Line), 220V/230V/240V (phase voltage)
Range of VoltageDefault -20%-+15%; -40%-+25% Optional
Overload Capacity125% long time operation; 130% last for 10 minutes;
150% last for 1 minute; 150% > load last for 300ms
110% long time operation;
110% < load < 130% last for 10 minutes;
130% < load < 150% last for one minute;
150% > load last for 300ms
OutputRated Output Voltage380/400/415VAC (Line-Line); 220/230/240VAC (phase voltage)
Rated Frequency50/60Hz
Output Power Factor1
Voltage Accuracy1.50%
Output Dynamic Response<5% (20%-80%-20% load step)
Dynamic Recovery Time<20ms (0%-100%-0% load step)
Output Total Harmonic Distortion<1% (linear load) , <5.5% (nonlinear load)
Inverter Overload102% long time operation; 110% transfer to bypass after 1 hour; 125% transfer to bypass after 10 minutes;
150% transfer to bypass after 1 minute; > 150% transfer to bypass after 200 ms
Frequency Accuracy0.10%
Range of TrackingAdjustable, ±0.5Hz-±5Hz, Default ±3Hz
Speed of TrackingAdjustable, 0.5Hz/S-±3Hz/S, Default 0.5Hz/S
Peak Ratio3:01
Three-Phase Accuracy120°±0.5°
SystemEfficiencyMain mode: 95% Max; Economic mode: 98%; Battery mode: 94.5%
ScreenLCD+LED+color touchscreen, 9-inch
LanguageChinese, traditional Chinese, English, Russian, Italian, Spanish, German
Protection RatingIP20
Communication InterfaceRS232, RS485, dry contacts, SNMP cards (option), emergency shutdown
Wiring MethodsBack and down wiring, optionalDown wiringBack and down wiring, optionalDown wiring
Working Environment0-40℃ (working temperature) ; -25℃~70℃ (storage temperature) ; 0-95% (no condensation)
Noise (dB) / m<56dB
Type of Cabinet2-modular cabinet4-modular cabinet6-modular cabinet2-modular cabinet3-modular cabinet6-modular cabinet
Size (W*D*H) (mm)Main Body485*697*398 (7U)485*697*575 (11U)485*751*1033 (22U)485*697*398 (7U)485*751*575 (11U)485*751*1033 (22U)
Main Body (put into server rack)485*697*308 (7U)485*697*485 (11U)485*751*928 (21U)485*697*308 (7U)485*751*485 (11U)485*751*928 (21U)
Module436*590*85mm (2U)
Weight (kg)Main Body (with modules)73kg113kg175kg73kg119kg175kg
Module15.3kg (PM10X)15.5kg (PM15)

Hot Products

Product Application TRM series modular UPS power, the industry leading, all-digital power distributi...
Product Application TCRM series modular UPS power, the industry leading, all-digital power ...
Product Application TCHR33 series Rack mounted UPS is widely used in government, finance, communicat...
Product Application TCHR11 series Rack Mounted UPS is widely used in government, finance, communicat...
Product Application TCMC Series Rack mounted Air Conditioner is mainly intended to cool the servers ...
Inrow Air Conditioner Application TCMC series Column-type Air Conditioner is intended to cool the ...