TYHD-DTU distribution automation remote terminal with High-reliability software platform and Self-test

 

DTU power distribution network feeder automation device is with a hardware platform of 32 bits of microprocessor of high-performance, is with embedded real-time operation as a software development platform, also with characters of high stability and reliability , high performance,high intensity and low cost and easily installation.

DTU provides enough communication interface( 4 technical grade RS232 Serial ports, 2 of them can be equipped as RS485 ports,2 pieces of 10M Ethernet port,1 piece of USB port),main processor adapts technical grade 32 bits of high-performance processing chip, with specialized maintenance software, also can be remotely kept maintenance by specialized network, such as each CPU module is realized by bus. Main CPU module is as master station to control the whole communication process, the gathering CPU Module is as subsequent station, the communication rates is above 9600bps. Several device constitutes Ethernet bus through inner embedded industrial grade switch to make sure data processing and data exchange with sufficient bandwidth. ·

Distribution terminal assembly

The power distribution terminal is divided into a core measurement and control unit area, an operation panel area and a wiring terminal area according to functions, and an internal operation panel area is built in the battery. If you need to install communication equipment such as fuse box and carrier, the power distribution terminal can be equipped with a communication box. The functional area is divided as shown in the table below..

 

The key technical indexes:

Remote signal performanceRemote circuit voltageDC24V
Remote signal resolution£2ms
Remote signal anti-shake time0~60S, Level difference 1ms
Output performanceOutput modeRelay passive contact output
Output capacityDC24V/16A,AC220V/16A
Output pulse width0.05~60S, Level difference 1ms
Working power supplyVoltage of power supplyAC220V,range AC165~AC264V

DC220V, range DC200V~DC375V

Positive and negative pole adaptation

Back-up power supplyStorage battery/ super capacitor bank ,DC24V/DC48V,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

There is type test report for it, test items as following:

 

 

 

 

Type Test Items

 

1. appearance and structure 2.function 3. electrical device performance 4.low temperature performance 5.high temperature performance 6.alternating temperature humidity7.vibrationendurance 8.incline drop test 9. electrical device life 10. static electricity and elecro-discharge immunity test 11.radio frequency electromagnetic field radiated immunity test 12.surge impact immunity test 13. power frequency magnetic field immunity test. 14. Adjacent interference test 15.short-circuit withstand impact test 16. fire hazard test 17. power consumption test 18. protection grade test 19. gripping strength test of grip structure.

 

 

Hot Products

Electrical TEST Instruments and Apparatus with high resistance meter The Insulating Oil Dielectric ...
DTU power distribution network feeder automation device with high-performance DTU power distribution ...
DTU power distribution network feeder automation device with characters of high stability and ...