Chongqing HOPU Filtration Plant Manufacture Co.,ltd |
|
HOPU HJS-200 Automatic Transformer Tangent Delta Tester is a high-precision test instrument for testing the dielectric loss tangent value and capacitance of various high-voltage power equipment on-site or in laboratories such as power plants and power substations. Measurement on dielectric loss tangent value (tgδ) and capacitance of transformer, mutual inductor, reactor, capacitor, bushing and arrester
The instrument is an integrated structure, built-in dielectric loss test bridge, variable frequency voltage regulator power supply, step-up transformer and SF6 high stability standard capacitor. The test high-voltage source is generated by the inverter inside the instrument and used for the test of the tested product after being boosted by the transformer. The frequency can be changed to 45Hz or 55Hz, 55Hz or 65Hz, and the digital notch technology is adopted to avoid the interference of power frequency electric field on the test, and fundamentally solve the problem of accurate measurement under strong electric field interference. At the same time, it is suitable for occasions where generators are used for power supply detection after all power failures.
This device is a high accuracy tester to test tangent of dielectric loss and capacitance of various HV electrical equipments for generations and substations. It also applies to workshop, laboratory and R&D institutions.
1. LCD display, mass storage data, the instrument data can be exported through the U disk, and can generate a work report.
2. Many test modes: internal high voltage, external high voltage,
internal standard, external standard, positive connection method,
reverse connection method, self excitation method in a variety of
ways to test; under the high pressure of outside the standard can
do the high voltage of more than 10kV) dielectric loss test.
3. CVT test one-step process: to test the full sealed CVT
(capacitive voltage transformer) C1, C2 dielectric loss and
capacitance, to achieve the C2, C1 testing at the same. The
instrument can also test the CVT ratio and voltage angle
difference.
4. Multiple protections safe and reliable: with input voltage
fluctuation, output short circuit, overvoltage, over current,
temperature and other multiple protection measures.
5. The instrument can be used for measuring the high-voltage
electrical equipment of the non grounding or grounding, and can
measure the capacitance of the capacitor voltage transformer tgδ
and the main capacitor C1 and C2.
6. The instrument is equipped with high voltage transformer, and
takes safety protection measures against lightning, zero switching.
Product Parameters
High voltage output: 0.5~10KV | Each files to increase 500V, a total of twenty files, capacity: 1500VA |
Accuracy | tg δ: ±(reading*1.0%+0.04%) |
Cx: ± (reading*1.0%+1PF) | |
Resolving power | tg δ: 0.01%,Cx:1pF |
Measuring range | 0.1%< tg δ< 100% |
3PF<Cx<60000PF | |
10KV,Cx≤30000PF | |
5KV, Cx≤60000PF | |
Power supply | AC 220V±10% ,50±1Hz |
Measurement method | Power frequency: 50Hz |
Pilot frequency: 45Hz/55Hz Automatic frequency conversion | |
Harmonic adaptation | ≤ 3% |
Service condition | -15℃-50℃ relative humidity<80% |
Outline dimension | 460(L)*345(W)*350(H) |
Weight | 35KG |
Tel: +86 23 62538144
Fax:+ 86 23 62538144-3
Website: www.hopufiltration.com
Branch 2: www.oilfiltration123.com