Home Companies Shandong Green World International Trading Co., Ltd.

indoors high voltage vacuum circuit breaker

Shandong Green  World International Trading Co., Ltd.
Active Member

Contact Us

[China] country

Address: 1107B Huidong Building, Wenhua East Road, Shandong, China

Contact name:Li Zheng

Inquir Now

Shandong Green World International Trading Co., Ltd.

indoors high voltage vacuum circuit breaker

Country/Region china
City & Province shandong
Categories Battery Chargers
InquireNow

Product Details

 

The main characteristic:

1. Equipped with excellent permanent magnet construction. It uses (single) double steady magnetic circuit, which leave out the complex store energy, lock catch and so on mechanical device. The amount of parts reduces above 70% that increases the reliability and life of machine.

2. Primary galvanic circle is installed in epoxy resin insulating cylinder made by APG craft. It can prevent impact of external forces, dirty environment to arc extinguish chamber.

3. Use electronization intelligent control unit, with high reliability.

4. 50 thousand times mechanical life realize the free maintenance.

5. Ciruit breaker can be made handcart-type or fix-type, and it can coordinate with switchgear cubicle and be easy oil free transformed

 

Parameter:

 

NO.

Item Name

Unit

Value

1

Rated voltage

 

KV

 

12

2

Power frequency withstand voltage(1min)

42

3

Lightning impulse withstand voltage(Peak)

75

4

Rated frequency

Hz

50

5

Rated current

A

630,1250,1600,2000,2500,3150,4000,5000

6

Rated short circuit breaking current(Effective value)

kA

20

25

31.5

40

7

Rated short-time withstand current(Effective value)

20

25

31.5

40

8

Rated short circuit current lasting time

S

4

9

Rated peak withstand current(Peak)

kA

50

63

80

100

10

Rated short circuit making current(Peak)

50

63

80

100

11

Rated single/back to back capacitor bank breaking current

A

630/400

12

Mechanical life

Time

100000

13

rated short circuit current cut-off times

30

20

14

Rated operation sequence

 

★off-0.3 s –on-off-180 s –on-off             ☆off-180s –on-off-180 s –on-off

 

Hot Products

Specifications It totally abides to GB1984-2003-General Technical Conditions for Generator Circuit ...
Specifications It totally abides to GB1984-2003-General Technical Conditions for Generator Circuit ...
The main characteristic: 1. Equipped with excellent permanent magnet construction. It uses (single) ...
The main characteristic: 1. Equipped with excellent permanent magnet construction. It uses (single) ...
The main characteristic: 1. Equipped with excellent permanent magnet construction. It uses (single) ...
The main characteristic: 1. Equipped with excellent permanent magnet construction. It uses (single) ...