Shandong Green World International Trading Co., Ltd. |
|
The main characteristic:
1. Equipped with excellent permanent magnet construction. It uses (single) double steady magnetic circuit, which leave out the complex store energy, lock catch and so on mechanical device. The amount of parts reduces above 70% that increases the reliability and life of machine.
2. Primary galvanic circle is installed in epoxy resin insulating cylinder made by APG craft. It can prevent impact of external forces, dirty environment to arc extinguish chamber.
3. Use electronization intelligent control unit, with high reliability.
4. 50 thousand times mechanical life realize the free maintenance.
5. Ciruit breaker can be made handcart-type or fix-type, and it can coordinate with switchgear cubicle and be easy oil free transformed
Parameter:
NO. | Item Name | Unit | Value | |||
1 | Rated voltage |
KV
| 12 | |||
2 | Power frequency withstand voltage(1min) | 42 | ||||
3 | Lightning impulse withstand voltage(Peak) | 75 | ||||
4 | Rated frequency | Hz | 50 | |||
5 | Rated current | A | 630,1250,1600,2000,2500,3150,4000,5000 | |||
6 | Rated short circuit breaking current(Effective value) | kA | 20 | 25 | 31.5 | 40 |
7 | Rated short-time withstand current(Effective value) | 20 | 25 | 31.5 | 40 | |
8 | Rated short circuit current lasting time | S | 4 | |||
9 | Rated peak withstand current(Peak) | kA | 50 | 63 | 80 | 100 |
10 | Rated short circuit making current(Peak) | 50 | 63 | 80 | 100 | |
11 | Rated single/back to back capacitor bank breaking current | A | 630/400 | |||
12 | Mechanical life | time | 100000 | |||
13 | rated short circuit current cut-off times | 30 | 20 | |||
14 | Rated operation sequence |
| ★ | ☆ | ||
★off-0.3 s –on-off-180 s –on-off ☆off-180s –on-off-180 s –on-off |