Product Details

Hige Precision Shunt Resistor Current Shunt Resistor FL2-F 200A Calculator Ammeter Meter Gauge

 

1Technical data

Accuracy class0.5%
Rated current in one time5A-1000A
Rated voltage in 2 times75mV
Environment temperature influenceChange 10℃ each, shunt output
Overload capacity120% to rated current, continue 2h

 

2. Technology

(1) Surface coating: nickel plating.

(2) The surface of the resistor is coated: black amino baking enamel.

 

3. Specifications

1. Accuracy level :2-4000A, 0.5 level,5000-10000A, 1 level.

2. Environmental conditions: -40 ~ +60 °C, the relative temperature ≤ 95% (35 ° C)

3. Overload performance: 120% of rated current, 2 hours

4. Voltage drop: 75mV

5. Load heat: Temperature rise changes stabilized, rated current of 50A does not exceed 80 ° C; rated current of 50A does not exceed 120 ° C.

6. Pakeage included:

1 x 200A 75mV for DC Shunt Resistor

 

4. Material

Shunt resistor consist of manganin soldered or silver brazed to brass/copper blocks. The shunts are artificially aged after finishing and then tested on full load according to the stardand rigidly.

 

5. Notice

(1). Can't be touched the joint of the shunt and cable of primary circuit. Secondary voltage can't be sampled from non-sampling point.

(2). It won't be exceed 80% of rated current for long time working. A loop cable (or copper platoon) and shunt connection doesn't allow someone to contact resistance from the sampling point.

 

6. Outside drawing

 

7. Application Standards

StandardsContents
Environmental standardsStandards for the electronic industry of the People's Republic of China: SJ/T 11363-2006 quantity requirements. Eu: ROHS.
Tolerance standardThe tolerance size is not specified in accordance with the national standard for Chinese migrant workers and the national standard: GB/ t1804-2000 rough C execution of general tolerances for linear and angular dimensions without tolerance.
Product standardNational standard of the People's Republic of China: GB/ t766-1998 direct action simulation indicator electrical measuring instruments and their accessories professional standard of the People's Republic of China: JB/ t9288-1999 external attachment diverter.
Safety standardsIEC61010-1:190 safety requirements for measuring, controlling and laboratory electrical equipment. Part 1: general requirements.

 

8. Analogue products presentation

 

Hot Products

50HZ Low Voltage DC Contactor 24vdc Contactor Coil Current 200 Amp Available Any Way To Install 1. ...
DC AC High Current FL2-L 2000A For Digital Amp meter Analog Meter 1. Parameter Product name DC shunt ...
JQ - 200D(B) / 48 - 48BW 200 Amp An Electrically Controlled Switch DC Power Contactor For Communicat...
Adjustable Current Shunt Resistor Circuit FL2-F 200A Digikey for Current Analogue Amp Panel Meter 1. ...
Hige Precision Shunt Resistor Current Shunt Resistor FL2-F 200A Calculator Ammeter Meter Gauge 1. ...
High Precision FL2-F 100a 75mv Current Shunt Resistor in Ammeter for AMP Ampere Instrument Panel ...