Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

AC100V 120A Electric Meter Calibration 50VA Load One Phase

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

AC100V 120A Electric Meter Calibration 50VA Load One Phase

Country/Region china
City & Province beijing beijing
Categories Other Electric Power Tools
InquireNow

Product Details

energy meter calibration Test Set,advantageous accuracy,high voltage,3pcs or 2pcs meter synchronously,high harmonic

 

 

Electrical parameters
Accuracy class0.05%, 0.1%
Power supplyOne Phase AC 100-265V, frequency 50/60Hz.
AC Voltage Output
Range57.7V, 100V, 220V, 380V; max 500V
Adjustment range(0-120)%RG(1)
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability0.01%/120s
Distortion0.1% (Non-capacitive load)
Output loadmax 25VA
Measuring accuracy0.05%RG
AC Current Output
Range200mA, 1A, 5A, 20A, 100A; max 120A
Adjustment range(0-120)%RG
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability<0.01%/120s
Distortion≤0.1% (Non-capacitive load)
Output loadmax 50VA
Accuracy0.05%RG
Power Output
Active power output stability<0.01%RG/120s
Reactive power output stability<0.02%RG/120s
Active power measuring accuracy0.05%RG
Reactive power measuring accuracy0.1%RG
Phase Output
Output adjustment range0°-359.999°
Output adjustment fineness10, 1, 0.1, 0.01 as optional.
Resolution0.01°
Accuracy0.05°
Power Factor
Adjustment range-1 ~ 0 ~ 1
Resolution0.0001
Measurement accuracy0. 0005
Frequency Output
Adjustment range40Hz-70Hz
Output adjustment fineness5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution0.001Hz
Accuracy0.005Hz
Voltage /Current/Harmonic Setting
Harmonic number2-51times
Harmonic content0-40%
Harmonic phase0-359.99
Harmonic setting accuracy(10%±0.1%)RD(2)
Power Energy Measurement Error
Active power energy0.05%RG
Reactive power energy0.1%RG
Power Pulse Output
Power pulse typeactive pulse, reactive pulse
Active power pulse output5V,10mA
Power Pulse Input
Energy pulse typesupport active and reactive pulse, the highest frequency
power pulse input is 180K.
Mechanical parameters
Dimensions (W×D×H) (mm)455x440x150
Weight (kg)12
Environmental conditions
Ambient temperature-10°C to +40°C
Relative humidity35%-85%

Hot Products

HQ46 CABLE TYPE 500A MV OUTPUT AC CLAMP ON CURRENT PROBE Description The HQ46 AC Current Probe is ...
HQ15 HIGH-VALUE VOLTAGE OUTPUT AC CURRENT CLAMP SENSOR Description The HQ15 AC Current Probe is ...
Electrical parameters  Accuracy 0.05%, 0.1% Power Supply One Phase AC 180-265V, frequency 50/60Hz. ...
energy meter calibration Test Set,advantageous accuracy,high voltage,3pcs or 2pcs meter synchronousl...
600V Harmonic Electronic Test Equipment 20mA With 640×480 Display Electrical parameters  Accuracy 0...
FEATURES Store and display measured data; Optional 5A, 20A, 100A, 500A, 1000A, 2000A, 3000A current ...