Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Outdoor Waterproof Split Core Current Transducer 1500A Medium Voltage

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Outdoor Waterproof Split Core Current Transducer 1500A Medium Voltage

Country/Region china
City & Province beijing beijing
Categories Solar Chargers
InquireNow

Product Details

Outdoors waterproof 1500A medium voltage Φ55 permalloy split core current transformer

LZCK series current transformers are applicable for AC power system 35kV and measurement of current of power supply equipment below 10KV also can be used for microcomputer protection. This type of current transformer employs imported silicon steel which with high permeability as magnetic material, has the characteristics of Small magnetic circuit loss and can be split, its semicircular core and secondary windings employ high quality epoxy resin vacuum, casting in plastic-case which is flame retardance anti-moisture, stable performance, no maintenance.

 

Parameters 

Technical parameters
Standards

IEC60044-1; IEC 61869-2; NTC 2205; GB1208-2006;

ANSI C57.13

Accuracy Class0.5S, 0.5%, 1%, 3%
Range of primary rated current100-1500A

 

Range of Rated load≤10VA
Rated frequency50/60Hz
Rated secondary current5A or 1A
Rated short-time thermal current40kA, 1S
Rated continuous thermal current150%I1n
Secondary winding power frequency withstand voltage3kV, 1min
Safety Factor Rating(FS) <10
Output signal1A, 5A, 333mV, 1V or 5V(customized)
Cable length2.5m, 5m, 10m(customized)

Flame retardant ABS plastic shell inside, jaw waterproof apron.

Mechanical parameters

Aperture (mm)Φ55
Dimensions (W×D×H) (mm)180×138×52
Weight (kg)2
Working conditions
Operating temperature-35°C to +65°C, average not exceeding +40°C
Storage temperature-40°C to +70°C
Ingress ProtectionIP65
Environmentoutdoors or indoors
The Height of above sea level0- 3000m
Conditions

No existence of severely begrimed, erosive and

radioactive gas in the air. Continuous working under the rated current is allowed.

 

 

 

 

Hot Products

LZCG530-10 Protection relay device using 5P20 50/1A Zero Sequence Current Transformer Zero Sequence ...
LZCG530-10 Zero Phase Current Transformer, Ring net cabinet 5P10 Ratio 100A / 1A Zero Sequence ...
LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...
Outdoors waterproof 1500A medium voltage Φ55 permalloy split core current transformer LZCK series ...
LZCK-55 GFUVE 100A/5A IP67 Outdoor installation Split Core Clamp On Current Transformer Clamp-On ...
LMCK185-10 2000A /5A 0.5s IEC60044-1 IP67 Outdoor split core current transformer manufacturers ...