Product Details

GF302D1 Portable Testing Equipment For Electrical Energy Meters, electricity meters

 

The GF302D1 three phase portable energy meter test system consists of an integrated three phase current and voltage source(up to 500V/120A or 500V/20A) and built-in three-phase electronic reference standard of accuracy class 0.05%. Characteristic features of the GF302D1 are its wide measuring range, high accuracy and high tolerance to unwanted external influences. The equipment offers high functionality combined with an excellent menu guided operation via built-in keyboards and colored 7” touch LCD-display.

 

In order to test meters, particularly those of the 0.2s class, a testing device with a high degree of accuracy is required. The concept of individual on-site meter testing with current and voltage sources has become increasingly popular. Our test technology for meter testing is particularly versatile and suitable for on-site testing and for use as a laboratory test system.

Features

  • Accuracy class 0.05
  • 0-20A/0-500V, 0-120A/0-500V
  • Start testing and creep testing
  • Reference standard and power source integrated
  • Test by automatic or manual
  • 7 inch TFT touch screen
  • Weight light 15Kg
  • Recorder 500 sets energy meter data
  • Overload, short circuit, open circuit protection

Parameters

Electrical parameters 
Accuracy class0.05%, 0.1%
Power supplyOne Phase AC 100-265V, frequency 50/60Hz.
AC Voltage output 
Range(U1,U2,U3)57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range(0-120)%RG(1)
Adjust fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability0.01%/120s
Distortion0.3% (Non-capacitive load)
Output loadeach phase 30VA
Measuring accuracy0.05%RG
AC Current output
Range (I1, I2, I3 )200mA, 1A, 5A, 20A, 100A(optional)
Adjustment range(0-120)%RG
Adjustment fineness0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability<0.01%/120s
Distortion≤0.3% (Non-capacitive load)
Output load30VA
Accuracy0.05%RG
Power output 
Active power output stability<0.01%RG/120s
Reactive power output stability<0.02%RG/120s
Active power measuring accuracy0.05%RG
Reactive power measuring accuracy0.1%RG
Phase Output
Output adjustment range0°-359.999°
Output adjustment fineness10, 1, 0.1, 0.01 as optional.
Resolution0.01°
Accuracy0.03°
Power Factor
Adjustment range-1 ~ 0 ~ 1
Resolution10, 1, 0.1, 0.01 as optional.
Measurement accuracy0. 0005
Frequency Output
Adjustment range40Hz-70Hz
Output adjustment fineness5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution0.001Hz
Accuracy0.005Hz
Voltage /Current/Harmonic Setting
Harmonic number2-51times
Harmonic content0-40%
Harmonic phase0-359.99
Harmonic setting accuracy(10%±0.1%)RD(2)
Power Energy Measurement Error
Active power energy0.05%RG
Reactive power energy0.1%RG
Power Pulse Output
Power pulse typeactive pulse, reactive pulse
Active power pulse output5V,10mA
Power Pulse Input
Energy pulse typesupport active and reactive pulse, the highest frequency
power pulse input is 180K.
Mechanical parameters
Dimensions (W×D×H) (mm)495x390x195
Weight (kg)15
Environmental conditions
Ambient temperature-10°C to +50°C
Relative humidity35%-85%
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.

Selection guide

No.AccuracyVoltage rangeCurrent rangeWeight
302D1120010.10%0-500V0-120A22KG
302D11200050.05%0-500V0-120A22KG
302D112010.10%0-500V0-12A15KG
302D1120050.05%0-500V0-12A15KG
302D124010.10%0-500V0-24A16KG
302D1240050.05%0-500V0-24A16KG

Hot Products

LZCG530-10 Protection relay device using 5P20 50/1A Zero Sequence Current Transformer Zero Sequence ...
LZCG530-10 Zero Phase Current Transformer, Ring net cabinet 5P10 Ratio 100A / 1A Zero Sequence ...
LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...