Prefabricated Electric Compact Transformer Substation (American Box
Type Transformer)
Prefabricated Electric Compact Transformer Substation (American Box
Type Transformer) description
ZGS series substation is American type combined substation with
function of high voltage control, protect, power transformation and
distribution. Usually used in urban and rural power distribution
system .The high voltage load switch and high voltage fuse of this
product are installed in the oil of the transformer, with the two
structure: in same case with the transformer and in different case
with transformer. It can be used in high-rise buildings, building
in urban and rural areas, residential communities ,high-tech
development areas, small and medium size factories, mining areas,
oil fields, temporary construction sites, and other premises
Structure features of Prefabricated Electric Compact
Transformer Substation (American Box Type Transformer)
- The product contains transformer cubicle, HV cable outgoing cubicle
and LV cubicle four parts.
- The performance of transformer complies with the requirements for
low loss energy-saving transformer.
- HV side adopts terminal type load switch + fuse protection, fuse is
full-range protection fuse.
- Load switch and fuse shall be installed in transformer cubicle, use
insulation liquid of transformer as insulation medium and radiation
medium, which is of the advantages of compact structure and good
radiation capability. Meanwhile they can put in the same
compartment or in different ones.
- Outgoing of HV side adopts structure of HV dry type bushing
supporting copper bus to facilitate several cables to connect.
- The outgoing of LV side can outgo directly or arrange LV outgoing
scheme as per requirements of users.
- The body is welded by steel plate, through anti-rust process, with
beautiful appearance.
- HV operation compartment and LV compartment are separated by
compartment panel, the operative components in HV operation
compartment include: load switch, transformer tap changer,
protective fuse. The followings are installed in body: oil surface
temperature meter, oil level guage, pressure relief valve, oil
relief valve, oil sample valve, oiling plug, and all equipment in
LV system as per user’s requirement.
Prefabricated Electric Compact Transformer Substation (American Box
Type Transformer) Maintenance
- Transformer shall conduct oil sample withstand voltage and medium
loss test once a year.
- When the oil level is too low, it shall be re-oiled, the plate No.
of oil and the oil plate NO. in tank shall be the same.
- The lightning arrester shall conduct precautionary test once every
year near thunderstorm season.
- After the fusion of fuse, it shall check the fault cause and change
the fusing tube, the specification of fuse shall be chosen as per
rules.
- When change the fuse, it is necessary to open load switch of high
voltage side and switch of low side.
- When operate load switch live, to ensure safety, it is necessary to
use operating rod.
- Product is attached with packing list, qualified certificate,
Ex-work test report, installation and use introduction, electrical
apparatus principle drawing and secondary wiring diagram as well as
keys and other spare parts as per agreement.