Home Companies Ningbo Tian'an Jinghua Power Technology Co., Ltd.

420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect

Ningbo Tian'an Jinghua Power Technology Co., Ltd.
Active Member

Contact Us

[China] country

Address: 21/F, Building 1, No. 816,Jinghua Road, Hi-tech Zone,Ningbo, Zhejiang, P.R. China

Contact name:Tony ma

Inquir Now

Ningbo Tian'an Jinghua Power Technology Co., Ltd.

420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect

Country/Region china
City & Province ningbo zhejiang
Categories Other Switches
InquireNow

Product Details

420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect
 
420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect Description
GW7 series Isolator switch(disconnectors) are outdoor 3-phase high voltage equipment. They are used to change over power circuit and electrically isolate the repaired equipment under no-load condition. GW7 are type of 3 poles centre rotating and double horizontal breaks.
 
420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect Technical data
S/NItemUnitParameter
1Rated voltagekV72.5145252363420
2Rated insulation level      
3Rated power frequency withstand voltage (1 min)      
4To earthkV160275460210520
5Across open breakskV200275+85460+145210+210610
6Rated lightning impulse withstand voltage      
7To earthkV350650105011751425
8Across open breakskV410650+1201050+2001175+2951425+240
9Rated switch impulse withstand voltage (peak)      
10between phase/ to earthkV------1425/9501574/1050
11Across open breakskV------850+295900+345
12Rated frequencyHz50/6050/6050/6050/6050/60
13Rated currentA1250
2000
2500
3150
4000
1250/20002000
2500
3150
4000
5000

31,50
5,000

3150
14Rated short-time withstand currentkA
40
50
31.5/4050/63160160
15Rated peak withstand currentkA
100
125
80/100125/1606363
16Rated duration of short circuits44332
17Rated terminal mechanical load      
18Horizontal -logntitudinalN750/10001250150025002000
19Horizontal- verticalN500/75075010002000660
20Vertical forceN7501000125015001500
21Isolating switch bus capacity of switching
currents and opening/ closing
 100V, 1600A,
100 times
100V, 1600A,
100 times
300V, 1600A,
100 times

450V, 3200A, 3times
400V, 1600A,
100 times
300V, 1600A,
100 times
22Grounding switch induction current open/ closing capacity     
23Electromagnetic induction-typ current (current/ voltage)A/kV100/4 (80/2)100/6 (80/2)160/15 (80/3)1250/35 (160/10)160/10 (80/2)
24electrostatic induction current (current/ voltage)A/kV2/65/6 (2/6)10/15 (3/12)50/50 (18/17)18/20 (1.25/5)
25Times of opening and closingtimes1010101010
26isolating switch small current open/ closing capacity     
27capacitive currentA--1111
28Inductive currentA--0.50.50.50.5
29RIV radio interference voltageuV<500<500<500<500<500
30Creepage distancemm>1813
2248
>3625
4495
>6300
7812
>9450>10500
31Mechnical endurancetimes500050001000500010000
32Applicable altitudes <2000<2000<2000<3000<1000
33Motor operating mechanism      
34Model CJ2CJ2SRCJ2SRCJ2SRCJ2
35Motor voltageVAC 380
DC220
AC 380
DC220
AC 380
DC220
AC 380
DC220
AC 380
DC220
36Control circuit's voltageV
AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110

AC 220
DC220
DC110
37Opening time and closing times7+17+116+116+116+1
38Output shaft rotation 180180180180180
39Manual operating mechanism      
40Model CS11CS11SRCSSRCSSRCS
41control circuit voltageVAC 220AC 220AC 220AC 220AC 220

 
 
Structure and working principle of 420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect
Earth switch(see the right picture),the movement is by CJ -3 institutions operating lever to earth switch through a link after the conversion, driving a four-link active grounding arm rotation, due to the active arm and door type bracket and earthing pipe is composed according to the design requirements special four-link system, thus ensuring the earth switch in the closing process, the first rotary motion, near the closing position, linear motion upward, insert static inner contact, opening and vice versa.
 



















































Hot Products

AC Outdoor GW5 Anti Electrodynamic 1600A HV Disconnect Switch 126KV Overview GW5 (GT10)-126D/1600-40 ...
252kv 2500A High Voltage Disconnect Switch Disconnector Isolator GW23 General overview GW23(GT9)252D...
420kV 5000A HV Disconnect Switch Break Isolator Double Side 3 Phase Disconnect 420kV 5000A HV ...
Air Break 330kV Switch Disconnector Isolator 4000A Outdoor 40KA Product Description General GW7B ...
GW4-126D outdoor HV AC disconnecting switch 1. Product Introduction GW4-126D outdoor HV AC ...
Voltage Regulator Oil Immersed Power Transformer ONAF 110KV SZ 110kV Oil-immersed type power ...