(1) Separately set a ground lead wire of iron yoke clamp. Because
if the iron core touches the upper clamp to cause a multi-point
ground fault, the ground current only flows inside the iron core
clamp, and no current flows through the core ground lead, which
will cause the staff to mistakenly believe that the iron core has
not failed; After setting, no matter where the iron core touches
the clamp, it will form a loop through two grounding external
leads, so that the grounding current can be correctly detected
externally.
(2) The core ground plate is placed in the middle of the cross
section of the iron yoke. Placed in this way, no matter where the
iron yoke pull-insulated bolt is located and where the fault ground
point is, the maximum induced voltage of the loop is only 1/4 of
the turn voltage, and the maximum ground current at this time is
only about a few amperes, which is more than the core The grounding
lugs are much smaller when placed in other locations.
(3) If it is indeed necessary to place the core grounding lug at
other locations due to inconveniences such as on-site installation,
the insulating bolts of the iron yoke strap and the ground lugs
should also be placed diagonally to prevent large currents.