Home Companies Hebei Kaixiang Electrical Technology Co., Ltd

3 Ph Resistive Load Bank Testing Of Generator Sets 300 KW Power Load No Dummy Load

Hebei Kaixiang Electrical Technology Co., Ltd
Active Member

Contact Us

[China] country

Address: No33 Wangshan Road, Green Island Economic Development Zone, Shijiazhuang, China

Contact name:

Inquir Now

Hebei Kaixiang Electrical Technology Co., Ltd

3 Ph Resistive Load Bank Testing Of Generator Sets 300 KW Power Load No Dummy Load

Country/Region china
City & Province shijiazhuang hebei
Categories Generator Parts & Accessories
InquireNow

Product Details

3 Ph Resistive Load Bank 300 KW power Load no dummy Load
 
Product Description
 
Resistive load bank is a device which can simulate the real-life resistive loads and provides a rigorous test regime for power supplies from 1kW to 60MW.The “load” of a resistive load bank is created by the conversion of electrical energy to heat by power resistors. It mainly used to test and maintenance of Engine Generators, Storage Battery Systems, UPS Systems, Inverters, Ground Power Units, Auxiliary Power Units, Aircraft Power Generators, Wind Generators, Hydro Generators etc.
 
Technical Parameter
 

Rating Voltage/Frequency400VAC/50Hz, 3 phase 4 wire, line voltage 400V, phase voltage 230V
Rated PowerResistive load: 300kW
Installed CapacityResistive load: 300kW
Load Step1,2,2,5,10,10,20,50,100,100kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance(each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control PowerSingle voltage 220VAC 50Hz
Wire Connection

Load power supply input——Copper bar (star coupling “Y”)
Control power supply input——Connector-bar

InsulationF
Way of WorkingContinuous Working
Casing Dimensions and Coolingabout 1460*1980*1800mm (length*width*height) Forced air cooling,Horizontal inlet air and vertical cooling
WeightAbout 750kgs/set
TransportationHoisting, there are lifting lug in top of casing, also the wheel casters can be provided
Casing ColorGrey(RAL7035)or as you required
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤2500 meter
Atmospheric Pressure86~106kPa
ContactorSchneider


Product Advangent
 
(1) Communication Mode:RS485/ USB or RS232 interface for communication.
(2) Load Mode: manual load or automatic load
(3) Manual Load: input power and power factor, and load according to the preset value.
(4) Automatic Load: set several load stages and duration, then complete the process according this stages automatically. 0%- 25%,- 50%,- 75%, -100%
(5) Real-time Monitor: through software display main parameter value, such as voltage, current, power, power factor, frequency and time.
 
Application:
 
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment

 

 
 
 





























Hot Products

Change star angle AC400/690 voltage generator load bank 200kw 50Hz Product Description The system ...
3 Ph Resistive Load Bank 300 KW power Load no dummy Load Product Description Resistive load bank is ...
Load bank power 500kw 50HZ for testing the output power of generator Product Description The system ...
Factory 1000kw Resistive Load Banks 3 Phase 4 Wire 50Hz Frequency Product Description The system ...
Power banks 1250kw Dummy Load Bank with anti corrosion materials Product Description The system ...
1200kw Testing Electric Load Bank 380 V AC 50Hz with ISO CE certificate Product Description The ...