Intelligent dummy Load Bank 600kw for genset UPS testing

Introduction

AC400-600kW Dummy Load Bank  can accurately test output power and load capacity with all kinds of generators, generator sets for all main electrical parameters including the dynamic parameters tested.

System monitoring and load the cabinets of two parts, with the host computer with the use of intelligent, auto-complete for all the electrical parameters of the generator set special test, while generating charts, graphs and test reports, from full manual operation. Provides a scientific means of detection equipment for the power generators.

Application

AC400-600kW Dummy Load Bank can be used in a wide variety of applications , such as

Factory testing of turbines ,Factory testing of engine generator sets,Periodic excercising of

stand-by engine generator sets, Ups system testing,Battery system testing , Load optimization in prime power applications , To reduce wet stacking problems , 

Technical specification

Technical Parameters
Rating Voltage/FrequencyAC 400V/60Hz, 3 phase 4 wire
Max Load PowerResistive load: 600kW
Load StepResistive load: 11 steps, 1,2,2,5,10,20,20,50,100,200,200kW
Power Factor1
Load Tolerance(each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control Power SupplyAC400V/60Hz 3 phase 4 wire
Wire Connection

Load power supply input——Copper bar (star coupling)

Control power supply input——Amphenol connector

Communication InterfaceRS485,RS232
InsulationF grade
Way of WorkingContinuous Working
CoolingForced air cooling,Horizontal inlet air,Upward cooling
TransportationHoisting, there are lifting lug in top of casing and casters in bottom of load bank
DimensionAbout 1980mm×1460mm×1800mm(length*width*height)
WeightAbout 1000kgs
Operating Environment Parameter
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤2500 meters
Atmospheric Pressure86~106kPa
 
Main features
Overvoltage Protection: the input load voltage is over the safe threshold value, system unload automatically and give an alarm.

Short Circuit Protection and Over Current Protection: when short circuit, fuses in the load bank can insure to unload automatically.

Overheating Protection: temperature is over the safe threshold value, system unload automatically and give an alarm.

Smoke Fog Protection: If there is smoke fog in the container, system cut off load automatically and give an alarm.

Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.

Fan Delivery Protection: insufficient air volume with any fan 2450m³/h, system unload automatically and give an alarm.
Overload protection with fan: when any fan cannot normally work, the load bank can unload automatically and give an alarm.
Emergency Stop: manually press the Emergency Stop switch on the panel, then load bank is in locked state, and cannot do any operation.
Protection Switch: some protection with switch, when misinformation or in special need, user can close the corresponding protection function temporarily.
Safety Monitor: through indicator lights on main interface, user can monitor system state. When system abnormally stop and protect, software interface prompt the cause immediately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Products

6.6KV-6MW Dummy Load Bank With Frequency 60HZ And Best Performance Sales Introduction AC6.6KV...
1000 Kva Inductive or Resistive Dummy Load Bank for generator testing Introduction AC400V-1000KVA ...
2000 KW Dummy Load Bank with copper bar for UPS generator testing Introduction Dummy load bank main ...
6.6 KV 4MW Dummy Load Bank 3 Phase 3 Wire With 60 HZ Introduction AC6.6KV-4MW Dummy Load Bank is a ...
Intelligent dummy Load Bank 600kw for genset UPS testing Introduction AC400-600kW Dummy Load Bank ...
AC400-500kW Dummy Load Bank With Frequency 50HZ And Best Sales Introduction AC400-500kW Dummy Load ...