Resistive Load Bank 800kw For Backup Power Supply UPS Generator Testing
 
Product Description
 
1. our load bank an accurately test output power and load capacity with all kinds of generators.
2. System consists of testing / control and load bank, mainly includes AC load bank, data capture system, auto load/unload control system, heat dissipation device, assist control and PC software.
3. User can control load bank through local control panel, also through software
 
Technical Parameter
 

Rating Voltage/Frequency400VAC/50Hz, 3 phase 4 wire, line voltage 400V, phase voltage 230V
Rated PowerResistive load:800kW
Installed CapacityResistive load: 800kW
Load Step1,2,2,5,10,10,20,50,100,200,200,200kW, min step load: 1kW
PF(Power Factor)1
Load Tolerance (each step)±5%
Load Tolerance(overall)±3%
Display Precision0.5 class
Control PowerSingle voltage 220VAC 50Hz
Wire Connection

Load power supply input——Copper bar (star coupling “Y”)
Control power supply input——Connector-bar

InsulationF
Way of WorkingContinuous Working
Casing Dimensions and Coolingabout 1460*1980*1800mm (length*width*height) Forced air cooling,Horizontal inlet air and vertical cooling
WeightAbout 1000 kgs / set
TransportationHoisting, there are lifting lug in top of casing, also the wheel casters can be provided
Casing ColorGrey(RAL7035)or as you required
WorkplaceOutdoor
Ambient Temperature-10℃~+50℃
Relative Humidity≤95%
Altitude≤1500 meter
Atmospheric Pressure86~106kPa

 
Product Advangent
 
1. Communication Mode:RS485/ USB or RS232 interface for communication.
2. Load Mode: manual load or automatic load
3. Manual Load: input power and power factor, and load according to the preset value.
4. Automatic Load: set several load stages and duration, then complete the process according this stages automatically. 0%- 25%,- 50%,- 75%, -100%
5. Real-time Monitor: through software display main parameter value, such as voltage, current, power, power factor, frequency and time.
 
Application:
 
1. As the generator loading system
2. Periodic running test for standby generator
3. Ship battery charging/discharging system testing
4. The acceptance of new system and testing of servicing equipment

 

 
 
 

Hot Products

Load Bank 500kw for backup power supply generator testing Product Description 1. our load bank an ...
Resistive Load Bank 800kw For Backup Power Supply UPS Generator Testing Product Description 1. our ...
resistive load bank 1000kw for backup Thailand UPS generator testing Introduction AC400-1000kW is of ...
ac load bank 1200kw Portable Load Bank for UPS Generator testing Introduction AC400-1200kW Automatic ...
1250kva load bank used in UPS generator test in thailand Introduction AC400V-1250kvA Portable Load ...
500 Kva Generator Load Bank Low Noise 3 Phase Load Bank Introduction (1) According to the special ...