VDL006 GFCI | Ground Fault Circuit Interrupter

 

1. General

VDL006 residual current operated circuit breakers with overcurrent protection (RCBO) are suitable for lines with AC 50/60Hz, rated voltage 240V/415V, rated current up to 63A and for purposes of residual current protection, overload and short circuit protection. When any personal electric shock occurs or the circuit leakage current exceeds the predetermined value, the residual current operated circuit breaker can automatically cut off the power supply in a very short period of time, so that the safety of persons and electrical equipment can be operated. The residual current operated circuit breaker can be used for infrequent conversion of lines under normal conditions, and applied under occasions such as industrial, and commercial, high-rise buildings and residential houses.

 

 

 

 

2. Technical parameters

2.1 The tripping characteristic curves are as shown below.

 

2.2  Basic parameters

 

Standard

IEC/EN 61009-1

Main Specifications

Model No.

VDL006

Rated current In

6A, 10A, 16A, 20A, 25A, 32A, 40A

Classified by Type of Instantaneous Tripping

Type B: (3 ~ 5) In, Type C: (5 ~ 10) In

Poles

1P + N

Type (wave form of the earth leakage sensed)

Type AC, Type A

Mechanical features

Rated voltage Ue

AC240V

Frame size rated current In

40A

Rated residual operating current In

10mA, 30mA, 100mA, 300mA

Rated residual non-operating current Ino

5mA, 15mA,  50mA, 150mA

Rated short-circuit breaking capacity Icn

3000A, 4500A, 6000A

Rated residual making  and 

breaking capacity Im

500A

Electrical life

2,000

Mechanical life

2,000

Rated impulse withstand voltage Uimp

4000V

Connection

From top and bottom, from bottom and top

2.3  The residual current breaking times

In (A)

In (A)

Breaking time when the residual current assumes the following values (s)

In

2In

5In

5A, 10A, 20A, 50A, 100A, 200A, 500A(a)

It(b)

6~40

0.01, 0.03, 0.1, 0.3

0.1

0.05

0.04

0.04

0.04

a. For tests of 5A, 10A, 20A, 50A, 100A, 200A and 500A, the current values beyond the lower limit of over-current instantaneous tripping are not tested.

B. Tests are done when It is equal to the lower limit current of over-current instantaneous tripping of type B and type C.

3. Outline and installation dimensions (mm)

_______________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

GFCI | Ground Fault Circuit Interrupter

Product Description:

GFCI Circuit Breaker – RCBO Type B

This Ground Fault Circuit Interrupter (GFCI) circuit breaker is designed to protect people and property from ground fault damage. It features a Terminal Type of Push-in, a Voltage Rating of 120/240VAC, an Interrupt Rating of 10kA, a Trip Type of Thermal Magnetic, and an Amperage Rating of 15A.

The GFCI Circuit Breaker is the ideal choice for residential, commercial, and industrial applications where protection from electrical shock hazards is required. It is designed to detect ground faults and trip quickly to protect people and property from electrical shock. It also has a built-in test button to verify the GFCI is functioning properly.

The GFCI Circuit Breaker is UL Listed to UL 489, and is CSA Certified to C22.2 No. 5-04. It is designed for easy installation and features a highly visible red trip indicator to alert when a ground fault is detected.

This GFCI Circuit Breaker is rated for use in wet or dry locations and is designed to meet the highest safety standards. It is a great choice for protecting people and property from ground fault damage.

 

Features:

  • Product Name: GFCI Circuit Breaker
  • Indicator Light: Yes
  • Trip Type: Thermal Magnetic
  • Interrupt Rating: 10kA
  • UL Listed: Yes
  • Voltage Rating: 120/240VAC
  • RCBO Type A
  • RCBO Circuit Breaker
  • RCBO Circuit Breaker 10KA
 

Applications:

HAROK GFCI circuit breakers offer reliable and efficient ground fault protection. Our models, VRL01, VRL02, VRL03, VRL11, VAL003, VKL003, VDL006, VRL22, are designed with a frequency rating of 50/60 Hz and an interrupt rating of 10kA. Each breaker is equipped with an indicator light for easy monitoring, and features a 14-2 AWG wire gauge for optimal performance. HAROK GFCI circuit breakers also provide overload protection, in addition to their ground fault protection.

HAROK GFCI circuit breakers are the perfect RCBO Type B circuit breaker for any residential or commercial application, providing both ground fault and overload protection. Our circuit breakers are designed to meet UL 1053 standard requirements, and are the ideal choice for any circuit breaker needs.

HAROK GFCI circuit breakers are the perfect solution for any ground fault circuit interrupter needs. Our professional-grade GFCI circuit breakers are designed to provide the highest quality of protection, while also providing the added convenience of an easy-to-use indicator light.

 

Technical Parameters:

Product NameAttributes
GFCI Circuit BreakerGround Fault Protection: Yes
Terminal Type: Push-in
Number of Poles: 1 Pole
Frequency Rating: 50/60 Hz
UL Listed: Yes
Interrupt Rating: 10kA
Voltage Rating: 120/240VAC
Amperage Rating: 15A
Wire Gauge: 14-2 AWG
 

Customization:

Custom GFCI Circuit Breaker Service

Our HAROK GFCI Circuit Breaker is the perfect solution for your grounding fault circuit interrupter, RCBO circuit breaker, and GFCI circuit breaker needs.

  • Brand Name: HAROK
  • Model Number: VRL01, VRL02, VRL03, VRL11, VAL003, VKL003, VDL006, VRL22
  • Place of Origin: CHINA
  • Voltage Rating: 120/240VAC
  • NEMA Rating: NEMA 1
  • UL Listed: Yes
  • Product Name: GFCI Circuit Breaker
  • Indicator Light: Yes

Our GFCI Circuit Breaker is UL Listed and has an indicator light for easy identification. It is rated for 120/240VAC and is NEMA 1 rated. We offer a variety of models, including VRL01, VRL02, VRL03, VRL11, VAL003, VKL003, VDL006, and VRL22.

 

Packing and Shipping:

Packaging and Shipping of GFCI Circuit Breaker:

  • Product will be packaged in a cardboard box with a corrugated inner sleeve.
  • Product will be shipped via UPS, FedEx, or USPS with tracking number.
  • Product will be sent out within 1-2 business days upon order confirmation.

 GFCI | Ground Fault Circuit Interrupter

Hot Products

VKL11 ELCB Earth Leakage Circuit Breaker Type S Selective time delay 1. General 1.1 Function Control ...
VKL11 Earth Leakage Circuit Breaker(ELCB) NF SEMKO VDE KEMA 1. General 1.1 Function Control electric ...
VKL11 Earth Leakage Circuit Breaker(ELCB) UL1053 1. General 1.1 Function Control electric circuits. ...
VKL11 Earth Leakage Circuit Breaker(ELCB) type F 1. General 1.1 Function VKL11F Earth Leakage ...
*, *::before, *::after {box-sizing: border-box; } * {margin: 0; } html, body {height: 100%; } body ...
VAL003 GFCI | Ground Fault Circuit Interrupter 1. General VAL003 residual current operated circuit ...