VDL006 Residual Current Operated Circuit Breaker With Over-Current Protection 10000A 120V 15000A RCBO Type A

Country/Region china
City & Province zhejiang
Categories Battery Chargers
InquireNow

Product Details

RCBO | Residual Current Operated Circuit Breaker with over-current protection

 

 

VDL006 Residual Current Operated Circuit Breaker with over-current protection (RCBO)

(MCB sized 1 module with switched neutral)

 

1. General

 

VDL006 residual current operated circuit breakers are suitable for lines with AC 50/60Hz, rated voltage 240V, 120V, rated current up to 40A and for purposes of residual current protection, overload and short circuit protection. When any personal electric shock occurs or the circuit leakage current exceeds the predetermined value, the residual current operated circuit breaker can automatically cut off the power supply in a very short period of time, so that the safety of persons and electrical equipment can be operated. The residual current operated circuit breaker can be used for infrequent conversion of lines under normal conditions, and applied under occasions such as industrial, and commercial, high-rise buildings and residential houses.

 

2. Technical parameters

 

2.1 The tripping characteristic curves are as shown below. 

 

2.2 Basic parameters

 

 StandardIEC/EN 61009-1
Main SpecificationsModel No.VDL006
Rated current In

6A, 10A, 16A, 20A, 25A, 32A, 40A

Classified by Type of Instantaneous TrippingType B: (3 ~ 5) In, Type C: (5 ~ 10) In
Poles1P + N
Type (wave form of the earth leakage sensed)Type B
Mechanical featuresRated voltage UeAC240V
Frame size rated current In40A
Rated residual operating current I△n10mA, 30mA, 100mA, 300mA
Rated residual non-operating current I△no5mA, 15mA, 50mA, 150mA
Rated short-circuit breaking capacity Icn

3000A, 4500A, 6000A

Rated residual making and

breaking capacity I△m

500A
Electrical life2,000
Mechanical life2,000
Rated impulse withstand voltage Uimp4000V
ConnectionFrom top and bottom, from bottom and top

 

 

2.3 The residual current breaking times

 

In (A)I△n (A)Breaking time when the residual current assumes the following values (s)
I△n2I△n5I△n5A, 10A, 20A, 50A, 100A, 200A, 500A(a)I△t(b)
6~400.01, 0.03, 0.1, 0.30.10.050.040.040.04

a. For tests of 5A, 10A, 20A, 50A, 100A, 200A and 500A, the current values beyond the lower limit of over-current instantaneous tripping are not tested.

B. Tests are done when I△t is equal to the lower limit current of over-current instantaneous tripping of type B and type C.

 

 

2.4 The over-current protection characteristics

 

No.Rated current In (A)Initial stateTest current (A)Specified time (t)Expected resultRemarks
a6 ~ 40Cold state1.13 Int ≥ 1hNon-tripping 
bImmediately after sequence a1.45 Int < 1hTrippingIncrease to the specified current within 5s after test item a.
cCold state2.55 In1s < t < 60sTripping 
dCold state3 Int ≥ 0.1sNon-trippingType B
5 Int < 0.1sTripping
5 Int ≥ 0.1sNon-trippingType C
10 Int < 0.1sTripping

 

 

 

3. Outline and installation dimensions (mm)

 

 

 

Product Description:

RCBO Type A is a Residual Current Operated Circuit Breaker with over-current protection, designed to provide superior protection against electric shock hazard and fire risk. It features a Rated Frequency of 50/60Hz, a Rated Breaking Capacity of 6kA, and a Mechanical Life of 2000. It also features different Rated Residual Operating Currents of 0.01A, 0.03A, 0.1A, and 0.3A. In terms of Rated Short-circuit Breaking Capacity, it supports 230/240V at 6000A or 10000A and 120V at 15000A.

 

Features:

  • Product Name: RCBO Type A
  • Mechanical life: 2000
  • Rated Residual Current Operating Time: ≤0.1s
  • Frame size rated current Inm: 50A
  • Rated Breaking Capacity: 6kA
  • RCBO Circuit Breaker

 

Applications:

RCBO Circuit Breaker Type A is the perfect choice for a wide range of applications. Manufactured by HAROK and featuring models VRL22, VAL003, VKL003, VDL006, VRL11, VRL01, VRL02, VRL03, VK007LE, this circuit breaker provides superior performance and reliability. It has a rated impulse withstand voltage Uimp of 6000V and an electrical life of 2000. It is classified by type of instantaneous tripping as Type B (3 ~ 5) In and Type C (5 ~ 10) In. It has a rated frequency of 50/60Hz and the connection can be from top to bottom or from bottom to top.

With its superior performance, reliability, and wide range of applications, RCBO Circuit Breaker Type A from HAROK is the perfect choice for any project. It is ideal for use in residential, commercial, and industrial settings, and can be used in a variety of applications, from lighting to power distribution. Its robust design ensures it will perform reliably in the toughest conditions.

 

Technical Parameters:

PropertyValue
Rated Breaking Capacity6kA
Rated Residual Current Off-state≤0.1mA
Rated impulse withstand voltage Uimp6000V
Rated Current6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A
Mechanical life2000
Rated residual operating current I△n0.01A, 0.03A, 0.1A, 0.3A
Rated Residual Current On-state≤0.2mA
Rated voltage UeAC240V
Rated residual non-operating current I△no0.005A, 0.015A, 0.05A, 0.15A
Rated short-circuit breaking capacity Icn230/240V 6000A, 10000A; 120V 15000A

 

Customization:

HAROK provides RCBO Type A with overcurrent protection, including the Model Number VRL22, VAL003, VKL003, VDL006, VRL11, VRL01, VRL02, VRL03, VK007LE. This product is from China, with an Electrical life of 2000. The Rated Residual Current Off-state is ≤0.1mA, and the Rated Residual Current On-state is ≤0.2mA. It has a Rated Current of 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A.

RCBO Type A is a type of RCBO Circuit Breaker with Overcurrent Protection. It is designed to protect the circuit against overload and short circuits. It is important to use RCBO Type A for safety purposes, and it is a great choice for commercial, industrial, and residential applications.

 

Packing and Shipping:

Packaging and Shipping for RCBO Type A

 

The RCBO Type A is packaged and shipped in its original box, with a shock-resistant cushion inside. The box is securely sealed and labeled for identification purposes. The box also contains the product manual, warranty information and other product-related literature. The product is then wrapped in bubble wrap or shrink wrap for protection during transit. The package is labeled with the appropriate shipping information, including the destination address and the tracking information. The shipment is then sent to its destination via a reputable courier service.

 

 

 

 

Hot Products

RCBO | Residual Current Circuit Breaker with Overcurrent Protection VRL22 Residual Current Operated ...
RCBO | Residual Current Operated Circuit Breaker with over-current protection VDL006 Residual ...
Provides ground fault and arc fault circuit protection LED blinks on trip to show the last known ...