Home Companies Zhengzhou Great Electric Co.,Ltd.

4 Phase Voltage & 3 Phase Current Protection Relay Test Equipment With Fault Playback

Zhengzhou Great Electric Co.,Ltd.
Active Member

Contact Us

[China] country

Address: No.1207-1, Building #1, the National University Sci-Tech Park of Henan Province, No.11 Changchun Road, Zhengzhou, Henan 450000

Contact name:Tony Han

Inquir Now

Zhengzhou Great Electric Co.,Ltd.

4 Phase Voltage & 3 Phase Current Protection Relay Test Equipment With Fault Playback

Country/Region china
City & Province zhengzhou henan
Categories Other Electric Power Tools
InquireNow

Product Details

4 Phase voltage & 3 Phase current output Protection Relay Test Equipment With Fault Playback

 

Main Test of 4 Phase voltage & 3 Phase current output,

1.AC TEST 

2.DC TEST 

3.Harmonic Superposition Test

4.High-Low Frequency Test

5.Power Direction & Impedance Test

6.Synchronization Test

7.Full Group Test

8.Distance & Zero Sequence Protection

9.Characteristic of Impedance

10.Differential Protection

11.Differential Harmonic

12.Comprehensive Test of Line Protection of 6-35 KV Microcomputer

13.Fault Review

 

Technical Index of 4 Phase voltage & 3 Phase current output,

 

AC current source
Output accuracy0.5%
Output range3*(0-40A); 0-120A (three phases in parallel)
 Phase current which can get long-time working 10A
 Maximum output power of phase current: 420VA
 Maximum output power of three phase current in parallel: 900VA
 Permissible working time (when three phase current in parallel to get maximum output): 10s
Frequency (basic wave) range20-1000Hz
Harmonics times1-20 times
DC current source
Output accuracy0.5%
Current output0-+/-10A per phase; 0-+/-30A (three phase in parallel)
Maximum load voltage output20V
Output accuracy0.5%
Phase voltage output4*(0-120V)
Line voltage output0-240V
Phase voltage/line voltage output power80VA/100VA
Frequency (basic wave) range20-1000H
Harmonics1-20 times
DC voltage source
Output accuracy0.5%
Phase voltage output amplitude0-+/-160V
Line voltage output amplitude0-+/-320V
Phase voltage/line voltage output power70VA/140VA
Dimension400*300*180mm
Weightapprox 20KG
Power supplyAC 220V±10%,50/60Hz
Ambient temperature-10℃ ~ +50℃

 

 

Switch signal and time measurement

 

Switch signal input

7circuits

Idle contact: 1~20mA,24V

Potential contact access: “0”:0~ +6V; “1”:+11 V~ +250V

Switch signal output2 pairsDC:220V/0.2A;AC:220V/0.5A
Time measure

Test range: 0.1ms ~ 9999s , accuracy 0.1mS

Measurement range: 0.1ms ~ 9999s

Measurement accuracy:0.1mS

The factory inspection report

of Three-phase Relay Test Set

1.The AC power test of the device

1.1 the accuracy of outputing current amplitude

the accuracy and resolution of outputing current amplitude: 0~1A,0.001A,0~10A,0.01A,10A~Max.0.1A.Output range:0~40A.

 

Current(A)0.1A1 A5 A10A20 A30 A
IA0.10010.9985.00810.00820.01830.015
IB0.09981.0025.00310.00720.01330.017
IC0.10020.9974.9999.99619.99030.015

 

1.2The output residual current measurements

The output residual current measurements when the device has no output

 

Phases of currentIAIBIC
residual current(mA)0.0020.0030.019

 

2.The AC voltage test of the device

2.1 the accuracy of outputing voltage amplitude

the accuracy and resolution of outputing voltage amplitude 0~10V,0.001V,0~30V,0.01V,30V~60V or 75V,0.1V;60V or 75V 0.1V . Output range:0~120V

 

 

Phase of Voltage1V10V30 V60 V80 V100 V120V
UA0.99810.01430.01660.00580.011100.032120.031
UB1.00210.01530.01660.001

79.988

7

100.035

120.036

7

UC1.00110.01830.01560.00280.01399.978120.034

 

3.The test of Phase

 

Test setting90°180°270°
VA ,IA0.2°90.2°180.1°270.2°
Angular deviation0.2°0.2°0.1°0.2°
VB ,IB0.2°90.1°180.2°270.1°
Angular deviation0.2°0.1°0.2°0.1°
VC ,IC0.2°90.2°180.1°270.2°
Angular deviation差0.2°0.2°0.1°0.2°

 

 

 

4,The DC power test of the device

4.1 Accuracy of the current output

 

Current(A)0.10.51235
IA0.10010.50091.00122.00353.00565.009
IB0.09980.49921.00072.00123.00455.007
IC0.1002

0.5007

.

 

0.99962.00013.00214.997

 

 

5.other function

TypeResult
1,simulate all kinds of failure,reclosing function test,etcNormal
2, Switch parameters input /output checkingNormal
3,communicationNormal
4, The ac power outputNormal
5,interface of each functionNormal

 

6.Test equipment

● voltmeter,type:ESCORT3146A , accuracy 0.5magnitude

● ammeter,type:GB/T7676-1998 ,accuracy 0.5 magnitude

● Tektronix oscilloscope

● Multi-purpose digital meter,type:200MULTIMETER

● Millisecond meter,type:702-2

● Phase,No.:Multi-function watt-hour meter

7,Conclusion:

Through the above test result,the function of the relay protection tester can be meet the requirements of various specifications and the introduction. By the quality inspection department check to leave the factory !

 

 

 

Hot Products

Advanced Multifunctional Relay Test Set The MC3000F is the all-in-one test system for protection ...
IEC61850 Protective Relay Test Equipment Multifunctional Kit (digital) MC3000F Optical digital relay ...
4 Phase voltage & 3 Phase current output Protection Relay Test Equipment With Fault Playback Main ...
Protection Relay Test Kit MCRT43 Features High power & reliable amplifier Adopting DSP technology ...
4 Phase voltage & 3 Phase current output Protection Relay Test Equipment With Fault Playback Main ...
4 Phase voltage & 3 Phase current output Protection Relay Test Equipment With Fault Playback Main ...