20MHz-Portable Sweep Frequency Response Analyzer
System Introduction
The transformer winding deformation tester is used for power
transformer with voltage grade of 6kV and above and other
transformers with special purpose. The power transformer is
inevitably vulnerable to impulse of various fault short-circuit
current or physical collision in the process of operation and
transportation and the transformer windings may lose stability
under the powerful electro-dynamic force exerted by such
short-circuit current, which could result in permanent deformations
such as local distortion, swell or dislocation and will severely
affect safe operation of the transformer. Deformation of
transformer windings is measured with frequency response analysis
method according to national standard DL/T911-2016 for electric
power industry, i.e. detect amplitude-frequency response
characteristic of each transformer winding and make vertical or
horizontal comparison of the detection result to judge possible
deformation of the transformer winding based on change of
amplitude-frequency response characteristics.
Main Features
1. Characteristics of transformer windings are measured with
frequency sweep method. Deformations of
windings such as distortion, swell or displacement of 6kV and above
transformer are measured by detecting
amplitude-frequency response characteristics of each winding, not
requiring lifting of transformer enclosure
or disintegration.
2. Quick measuring, measuring of a single winding is within 2
minutes.
3. High frequency accuracy, higher than 0.001%.
4. Digital frequency synthesis, with higher frequency stability.
5. 5000V voltage isolation fully protects safety of the testing
computer.
6. Able to load 9 curves at the same time and automatically
calculate parameters of each curve and diagnose
winding deformations to provide the reference
diagnosis conclusion.
7. Analysis software has powerful functions and software and
hardware indicators .
8. Software management is humanized with high degree of
intelligence. You only need to click a key to
complete all measurements after setting of parameters.
9. The software interface is concise and vivid, with clear menus of
analysis, save, report export, print, etc.
Technical Index
Item | Technical Index |
Measuring speed: | 1 min- 2 min for single-phase winding |
Output voltage: | Vpp-25V, adjusting automatically in test |
Output impedance: | 50Ω |
Input impedance | 1MΩ (the response channel is built with 50Ω matching resistance) |
Frequency scan scope | 10Hz-20MHz |
Frequency accuracy: | 0.001% |
Frequency scan manner: | linear or logarithmic, frequency sacn interval and number of sweep
points are freely settable |
Curve display | amplitude-frequency curve (phase-frequency curve, optional) |
Width of measuring dynamic range | -120dB~20dB |
Supply voltage: | AC100-240V 50/60Hz (use DC12V Adapater recommend) |
Dimension | 238mm*184mm*40mm |
Net weight: | 2.45Kg |