Communicable Electrical Line Locator , Quick Automatic Power Failure Indication System

Country/Region china
City & Province beijing beijing
InquireNow

Product Details

TYHD-A3/110 OverheadLine Communicable Fault Indicator is applied to 110kV overhead line ,is a device to indicate line fault current. This system is composed of two parts, one is gathering unit and the other is collection unit.gathering unit monitors line running status real-time. When fault happened ,the gathering unit can quickly locate phase-phase short-circuit area,the fault line and fault point can be judged quickly and accurately.in the meantime, the alarm flag turn red and appear flashlight and the fault signal also be transmitted to collection unit. After receiving signal from gathering unit, the collection unit send the received data to master monitoring station through wireless communication (GPRS/CDMA etc.)

The master station monitoring software analyze the received data and network topology, then to confirm the fault location and appear audible and visual alarm signal, in the meantime, the master station send the analyzed fault information to the operator’s cellphone and help them to find the fault point quickly, it reduces the power-off duration and improve the power supply reliability.

Technical specification

1. invironemenatal index:

1) ambient temperature:-40~70℃

2) Relative humidity:5~100%

3) atmospheric pressure:70kPa~106kPa

4) altitude:<2000m

5) pollution grade:not lower than grade V.

2. System index:

1) System voltage:≤110kV

2) System frequency:50Hz

3) conductor cross-section:35~240 mm2

4) suitable for maximun over-current protection delay:3S

3. Main technical performance and parameters

3.1 gathering unit

1) short-circuit judgement accuracy rare:100%;

2) short-circuit alarm current minimum lasting time recogizable:between 20ms~40ms;

3) alarm error:short-circuit alarm starting error≦±10%,

4) wilrless communication distance:≤20meter;

5) Average power consumption:<30μA;

6) Running life:running continuously 10 years;

7) net weight:≤0.5kg;

8) protection grade:IP68;

3.2 collection unit

1) rated working voltage:DC 6V/DC 12V;

2) connection numbers for gathering units:9 pcs of gathering units;

3) timing accuaracy:≤1s/24h;

4) average non-fault time(MTBF):>70000 hours;

5) communication module equipped:4G/3G/2G;

6) solar panel capacity:≧12W(equipped by local standard);

7) stand-by battery capacity:≧12AH(equipped by local standard)

8) Protection grade:IP65;

9) weight:<5Kg;

10) installtion mode:hoop fixation;

Installation and uninstalltion:

Insatallation :

a) By fitting the bracket installed in the hot sticks, screw detaching sheet nut to let the sheet fully retracted into the interior of the column (ie: try to tighten the sides, leaving enough space so as not to block the indicator when installing).

b) put the indicator into the bracket , and make the spring device to hook with the indicator spring, and rotate the spring device down firmly until after the indicator spring pulled position retractor can hook, then hook the spring with retractor and pull t he spring device out. And use the same method to the other side of the same end of the indicator spring to hook retractors.

c) Aligning the overhead lines pushed up and under the pressure of the overhead lines the indicator springs are divorced from the retractor spring and stucked overhead lines firmly.

There is type test report for it, test items as following:

 

 

 

 

Type Test Items

 

1. appearance and structure 2.function 3. electrical device performance 4.low temperature performance 5.high temperature performance 6.alternating temperature humidity7.vibrationendurance 8.incline drop test 9. electrical device life 10. static electricity and elecro-discharge immunity test 11.radio frequency electromagnetic field radiated immunity test 12.surge impact immunity test 13. power frequency magnetic field immunity test. 14. Adjacent interference test 15.short-circuit withstand impact test 16. fire hazard test 17. power consumption test 18. protection grade test 19. gripping strength test of grip structure.

Hot Products

optical fiber communicable fault indicator for underground used for output wireless signal The TYHD...
optical fiber communication earth fault indicator with automatically identify and effection TYHD-A1 ...
The cable indicator of short circuit fault for the cable 35kV system with shorten power-off time The ...
cable earthed fault indicator system with function of zero-sequence current measurement and data ...
TYHD-A3/110 OverheadLine Communicable Fault Indicator is applied to 110kV overhead line ,is a device ...
Safety criterion Welcome to use remote transmission unit manufactured by us. Each remote terminal ...