Home Companies Beijing Tianyihongda Science & Technology Development Co., LTD

Stainless Steel Pole Mounted Switch , Vacuum Circuit Interrupter Switch

Beijing Tianyihongda Science & Technology Development Co., LTD
Active Member

Contact Us

[China] country

Address: Room1301, Building 11, yard 88 , Sanluju Road, Fengtai District, Beijing, China

Contact name:

Inquir Now

Beijing Tianyihongda Science & Technology Development Co., LTD

Stainless Steel Pole Mounted Switch , Vacuum Circuit Interrupter Switch

Country/Region china
City & Province beijing beijing
Categories Battery Chargers
InquireNow

Product Details

Circuit breaker technical parameters:

 

 

S/N

Name

 

Unit

Data
12kV24kV
1Rated VoltagekV1224
2Rated FrequencyHz5050
3Rated currencyA630 1250630 1250
4Rated short-circuit breaking currentkA20 25 31.520 25 31.5
5Rated peak withstand currentkA50 63 8050 63 80
6Rated short-time withstand current / durationkA/S20/4 25/4 31.5/420/4 25/4 31.5/4
7Rated short circuit closing current (peak)kA50 63 8050 63 80
8Rated operation sequencetimes0-0.3S-C0-180S-CO0-0.3S-C0-180S-CO
9Mechanical lifetimes1000010000
10Rated short-circuit breaking current breaking timestimes3030
111min Power frequency withstand voltage(wet) phase, ground/fracturekV34/3564/50
(dry) phase, ground/fracturekV42/4965/79
12Lightning impulse withstand voltage (peak) phase to phase, phase to ground / fracturekV75/85125/145
13Secondary circuit 1min power frequency withstand voltageV20002000

 

Main mechanical characteristics of the circuit breaker

 

 

S/N

Name

 

Unit

Data
12kV24kV
1Contact opening distancemm9±112±1
2Contact over-travel distancemm2+1-0.53±1
3Opening speedm/s1.4±0.21.4±0.2
4Closing speedm/s0.6±0.20.7±0.2
5Contact closing bounce timems≤2≤2
6Distance between the phasemm340380
7Different period of three phase closing(opening)ms≤2≤2
8Main circuit resistance per phase / with CT / with CT band isolationμΩ≤50/≤70/≤120≤50/≤70/≤120
9Closing timems30~6025~60
10Opening timems20~4520~50
11Energy storage motor rated powerW4070
12Circuit breaker body weightkg7085

Switch appearance and size

 

Hot Products

Safety criterion Welcome to use remote transmission unit manufactured by us. Each remote terminal ...
Welcome to use remote transmission unit manufactured by us. Each remote terminal uint has already ...
smart Outdoor column SF6 isolation load break switch installed on pole 1. Normal service conditions ...
high voltage electrical SF6 Gas Insulation three-phase Linkage pole mounted switchHigh with pressure ...
Circuit breaker technical parameters: S/N Name Unit Data 12kV 24kV 1 Rated Voltage kV 12 24 2 Rated ...
ZW32 HV.AC outdoor automatic circuit breaker is combined of ZW32 vacuum circuit breaker and CH4 ...