1.CKVB-24/GE is the circuit breaker with right lateral operating mechanism.

 

2. Working Condition

2.1 Ambient air temperature: -25℃~+40℃

2.2 Ambient humidity:

---- relative average daily humidity: ≤95%

---- relative average daily water vapor pressure: ≤2.2kPa

---- relative average monthly humidity: ≤90%

---- relative average monthly water vapor pressure: ≤1.8kPa

2.3 Altitude: ≤1000m

2.4 Earthquake intensity: ≤magnitude 8

2.5 Ambient air doesn’t obviously pollute by dust, smoke, corrosive or combustible gas, vapors or salt spray.

(Exceeding above working condition is available as customized product)

 

3.Technical Data

DescriptionUnitParameter
Rated voltagekA24
Rated short-time withstand voltagephase-to-phase phase-to-earthkA65
open contactkA79
Rated lighting impulse withstand voltagephase-to-phase phase-to-earthkA125
open contactkA145
Rated frequencyHz50
Pole centre distancemm210, 230
Rated currentA6301250
Rated short-time withstand current(4s)kA2531.52531.5
Rated peak withstand currentkA63806380
Rated short-circuit breaking currentkA2531.52531.5
Rated short-circuit making currentkA63806380
Rated breaking cable charging currentA25
Rated capacitor bank inrush making currentkA12.5
Rated single capacitor bank breaking currentA630
Rated back to back capacitor bank breaking currentA400
Operating sequence/Opening-0.3s-Closing/Opening-180s-Closing/Opening
Mechanism lifetimes20000
Opening times for rated currenttimes20000
Opening times for rated short-circuit currenttimes50
Clearance between open contactsmm13±1
Overtravelmm4±1
Average closing speedm/s0.8~1.2
Average opening speedm/s1.1~1.7
Closing timems35~70
Opening timems20~50
Bounce time for contact’s closingms≤2
Asynchronous time for three-phase contacts closing / openingms≤1
Allowable accumulated wearing thickness of moving/fixing contactmm3

4. Standard

---- GB1984-2003

---- IEC60056-2001

---- GB/T16927-1997

---- GB/T 4473-2008

---- DL/T403-2000

---- JB/T3855-2008

 

 

Hot Products

1. CKVB-12/GC is withdrawable circuit breaker. 2. Working Condition 2.1 Ambient air temperature: -25...
1. CKVB-12/GD is fixed/withdrawable circuit breaker. 2. Working Condition 2.1Ambient air temperature...
1.CKVB-24/GE is the circuit breaker with right lateral operating mechanism. 2. Working Condition 2.1 ...
1.CKVB-24/GB is the withdrawable circuit breaker. 2. Working Condition 2.1 Ambient air temperature: ...
1. Fixed circuit breaker CKVB-12/GA 2. Technical Data Description Unit Parameter Rated voltage kV 12 ...
1. Withdrawable circuit breaker CKVB-12/GC 2.Technical Data Description Unit Parameter Rated voltage ...