Home Companies Tianjin Estel Electronic Science and Technology Co.,Ltd

IP55 Outdoor Cabinet Air Conditioner Active Cooling RS485 Communication Alarm Output

Tianjin Estel Electronic Science and Technology Co.,Ltd

Contact Us

[China] country

Trade Verify

Address: Shenzhen, China

Contact name:Fiona Liang

Inquir Now

Tianjin Estel Electronic Science and Technology Co.,Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

IP55 Outdoor Cabinet Air Conditioner Active Cooling RS485 Communication Alarm Output

Country/Region china
City & Province shenzhen guangdong
Categories Circuit Breakers
InquireNow

Product Details

IP55 230VAC 50Hz 300W Outdoor Cabinet Air Conditioner Active Cooling RS485 Communication Alarm Output Dry Contact

 

 

1. Outdoor cabinet air conditioner introduction

 

The air conditioner is one kind of refrigeration product self-developed for cabinet. It is applicable in the place where the cabinet internal heat is very large, the internal electronic equipment is sensitive to the environment temperature and which should be isolated internally and externally completely. This product has multiple functions, high reliability, and has the feature that it can start to work without complex debugging after powering.

 

The fan in the internal cycle air path absorbs the hot air from the upside to make air heat exchange by evaporator fins, and sends the cooled air from the downside of the air conditioner. By so, the air in cabinet can cycle to achieve the purpose of lowering the temperature. Meanwhile, The fan in the external cycle air path absorbs the external cold air from the downside, and discharges the hot air from the upside after heat exchange.

 

 

 

2. Technical parameter

 

ItemNameUnitParameter
Dimension and installationBody outline dimension (height*width*depth )mm550*320*169

Outline dimension including

flange(height*width*depth )

mm582*352*169
WeightKg12.5
Installation methodDoor Mounted
Application environmentOutdoor
Environment and protectionWorking environment temperature-40 to +55
NoisedB(A)54
IP gradeIP55
RefrigerantR134a
ROHS certificationyes
PerformanceInput voltage range220±15%VAC~50Hz
Refrigerating capacity(L35/L35)W300
Rated Refrigerating input power(L35/L35)W235
Rated Refrigerating current (L35/L35)A1.1
Maximum Refrigerating currentA1.6
Heat capacity(optional)W300
Air Volume of Inner Circulationm3/h135
 

 

 

3. Applications

 

The environment of outdoor cabinet is dusty and humid, in order to ensure the clean environment of equipment, it is necessary to use air conditioner to isolate the inside of cabinet from the outside environment. Prevent the entry of foreign matters. At the same time, it can prevent the equipment from being damaged by overheating. Ensure that the equipment has a good operating environment.

 

 

4. Feature

 

(1) Compact structure and small volume
(2) Using famous compressor, because the cabinet air conditioning is generally need to work for a long time, the compressor requirements for air conditioning are very high.
(3) Environmental refrigerant
(4) Low noise
(5) Microcomputer digital display: the cabinet belongs to the unattended type. In order to remotely view the operation status of the equipment and the cabinet temperature, and avoid manually starting the air conditioner on site and setting the temperature point, the air conditioner cabinet has the functions of setting the cabinet temperature, fault code display, low voltage, overheat and over-current fault protection and alarm, etc.

 

5.​ Installation size drawing

 

6.  Electrical installation

 

(1) Power input port

 

 

ItemPortDefinition
LiveLpower input cable L
NullNpower input cable N
EarthPEEarth line
 
 
(2) Alarm output and signal input port
 
ItemPortDefinition
+ RS485 communication interfaceRS485ARS485 communication ports (+)
- RS485 communication interfaceRS485BRS485 communication ports (-)
The public alarm dry nod (NO)NOIt is normally open if no alarm
The public alarm dry nod (COM)COMcommon port
The public alarm dry nod (NC)NCIt is normally close if no alarm
Hydrogen discharge / emergency fan dry contact (NO) (Optional)1It is normally open if no output
Hydrogen discharge / emergency fan dry contact COM (Optional)2Hydrogen discharge / emergency fan dry contact COM
 

7. Remote monitor

Air conditioner has an RS485 communication interface, supporting MODBUS- RTU communication protocol. The air conditioner communicates with the upper monitor through the RS485 communication interface. Or users can check the air conditioner’s running state by viewing the display screen directly and change its running parameters.

 

8. Display interface

 

9. Air conditioner picture

 

 

 

10. Package

 

Carton + wooden pallet

 

 

 

 

11. Production Process

 

 

 

Hot Products

IP Rated Air Conditioned Telecom Cabinet Outdoor Rack 46U Powder Coated Enclosure Application The ...
IP55 Waterproof Outdoor Telecom Cabinet 20U 19 Inch One Front Door 1500W Air Conditioner Anti-Theft ...
IP55 Fan Cooling Pole Mount Outdoor Power Supply Cabinet UPS Backup Power System Enclosure ...
Waterproof Dusproof 42U Fan Ventilation Outdoor Telecom Cabinet W×D 600mm×600mm Communication Base ...
IP55 230VAC 50Hz 300W Outdoor Cabinet Air Conditioner Active Cooling RS485 Communication Alarm ...
Front Rear Access 32U 19 Rack Double Door Sheet Steel Powder Coated Air-Con Telecom Outdoor Cabinet ...