Water-cooling Antspace HK3 parameter specifications
Product OverviewInput voltage415V±10% /60Hz /3P /N /PE
Total power consumption(Two power distribution cabinets share the load)≤1100kW
MinerMiner inlet/outlet water temperature35°C/45°C
ContainerSupporting power consumption (cooling, power distribution)52kW1000kW

Container dimension

(length * width * height)

6058mm*2438mm*2896mm
Cooling tower dimension (length*width*height), 5800mm*2240mm*4286mm(Without guardrails)
Weight (container with miner weight)12Ton
Weight(Cooling tower operating weight)12Ton
Number of miners210Units
Spray pump flow230m³/h
Heat dissipation capacity1000kW
Temperature variation between inlet and outlet(heating side)ΔT10°
Cooling tower docking interface specificationsDN125
Heating docking interface specificationsDN100
Cooling tower inlet water pipe specificationsDN40
Cooling tower drainage pipe specificationsDN65
Heating side pressure capacity10Kg
Design flow of heating side85m³/h
Maximum inlet/outlet water temperature on heating side35/45
Heating side design ΔT40/50
Operating Environment RequirementsAmbient temperature-25°C~45°C
Noise78dB(internal) / 65dB (external)
Internal coolantSpecifications are selected based on local environmental conditions
Water Consumption1.15m³/h(Water consumption of external spray, closed when the ambient temperature is below 10°C)

 

The energy consumption of Antminer s19 pro hyd is 5,445 W, and the energy efficiency is 27.5 J/TH. With such a huge energy consumption, Bitmain recommends users to use their specially designed mining machine storage cabinet Antspace HK3. This container-like mining rack provides 1MW power supply can supply 210 sets of S19 PRO Hyd mining machines.

 

Advantages of Antspace HK3

  • High-density design: 1MW heat dissipation capacity + supports up to 210 water-cooled mining machine positions for Antspace HK3 @20HC.
  • Flexible heat dissipation scheme: DWT-T Dry-Wet Tower Traditional Type can be selected for Antspace HK3.
  • High efficiency and energy saving: PUE is as low as 1.03; optional heating components can provide heat recovery; frequency conversion fan control reduces water consumption, energy consumption and noise for Antspace HK3.
  • Intelligent control: manual/automatic dual-mode control; fully closed-loop water temperature automatic control in automatic mode keeps the mining machine in the best working condition; supports online mining machine power on/off/online program upgrade/online initiative.
  • Safe and reliable: the whole system has passed cTUVus certification, and the container body has passed CCS classification society certification; condensation and leakage detection/alarm; cooling tower cage ladder and guardrail meet OSHA standards; Lock design, remote video monitoring, GPS positioning, one-button emergency stop, electric cabinet interlocking design.
  • Convenient operation and maintenance: the Antspace HK3 network on both sides of the shelf is controlled by two sets of switches; each mining machine can be powered off separately; the water inlet and outlet of each mining machine can be opened and closed independently, and each has only one; The impact on other mining machines when the dimension needs to be powered on and off and taken off the shelf.

Specification for Dry-Wet Towers DWT-T and DWT-C

Product OverviewValue
TypeDry-Wet Tower Traditional Type (DWT-T)Dry-Wet Tower Container Type (DWT-C)
Dimensions(L*W*H)5800mm*2240mm*4200mm6058mm*2438mm*2896mm
Heat Dissipation Capacity1000kw1000kw
Outlet Temperature @ 28℃ Wet Bulb Temperature, 3535
Container CertificationNoneChina Classification Society Certification
Safety CertificationNorth America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1
Operating Power14kw~28kw14kw~28kw
Motor Rated Voltage and Frequency415V±5% 60Hz(North America)
400V±5% 50Hz(EU,Middle East)
415V±5% 60Hz(North America)
400V±5% 50Hz(EU,Middle East)
Detailed CharacteristicsValue
Shipping Weight5T6T
Operating Weight9T10T
Connection InterfaceDN125(GB/T 9119-2010 PN16 DN125)DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe InterfaceDN40(Internal thread)DN40(Internal thread)
Drain Pipe InterfaceDN65(Internal thread)DN65(Internal thread)
Noise Level @25℃, 16m7070
Water Consumption1m³/h~1.5m³/h1m³/h~1.5m³/h

 

 

 

WX20220905-151306@2x.png