Universal Protection Relay Test K2063i Fully Function KRT Software Testing Modules

City & Province shenzhen guangdong
Categories Measuring & Analysing Instrument Processing Services
InquireNow

Product Details

  • Universal Relay Test Applications
  • 6x35A & 4x310V independent high burden output channels
  • Lightweight, <20Kg
  • Inbuilt 9.7” True color TFT LCD with touch screen, numerical and shortcut keyboard, fully control with / without laptop
  • GPS / IRIG-B code synchronize end-to-end testing
  • Fully function KRT software testing modules
  • 3-Years guarantee of free repair and life-long maintenance
  • Free software upgrade
  • Optional function for energy calibration, 13 Channels Low-Level outputs etc

 

Ordering Ref.

 

ModelCurrent OutputsVoltage Outputs
K20666×30A @ 450VA max / 3×60A @ 850VA max7×130V @ 75VA max
K2066i6×35A @ 450VA max / 3×70A @ 850VA max7×310V @ 90VA max
K20636×30A @ 450VA max / 3×60A @ 850VA max4×130V @ 75VA max
K2063i6×35A @ 450VA max / 3×70A @ 850VA max4×310V @ 124VA max
K20303×30A @ 450VA max4×130V @ 75VA max
K2030i3×35A @ 450VA max4×310V @ 124VA max
 

 

 

Characteristic

  • 10 Channels (4V + 6I) outputs, Each output channels are independent and simultaneous control of magnitude, Phase angle and frequency values, able to inject DC, AC sine wave and up to 20x harmonics.
  • Variable battery simulator, DC 0-310V, 124Watts max.
  • Graphical test modules and templates for testing of various relays
  • Quick relay testing facility in Manual mode
  • Shot/Search/Check, Point & Click testing
  • RIO/XRIO import & export facility
  • Switch on to fault test(SOTF)
  • Power system model for dynamic testing
  • Inbuilt GPS / IRIG-B sync end-to-end testing
  • Online Vector display
  • Automatic test results assume
  • Automatic test report creation
  • Self-protect for wrong power supply up to 450V AC/DC input.
  • Anti-clipping detect, Wrong wiring connect alarm and self-protect, overload and overheat protection

 

 

Parameters

Voltage Outputs
Output Range & Power4×310 V ac (L-N)124 VA max each
2×620 V ac (L-L)248 VA max each
3×310 V dc (L-N)124 W max each
Accuracy

±2 mV @ 0.2~2 V ac

<0.07%Rd+0.03Rg Guar. @ 2~310V ac

<0.03%Rd+0.01Rg Typ. @ 2~310V ac

±10mV @ 0.5 V~5 V dc

±0.5% @ 5 V~310 V dc

Resolution1mV
Distortion<0.1% Guar. / <0.05%Typ.
Current Outputs
Output Range & Power6×35A ac (L-N)450 VA max each
3×70A ac (2L-N)850 VA max each
1×180A ac (6L-N)1200 VA max
3×20A dc (L-N)300W max each
Accuracy

±1 mA @ 0.2A~0.5A ac

<0.15%Rd+0.05Rg Guar. @ 0.5~35A ac

<0.05%Rd+0.02Rg Typ. @ 0.5~35A ac

±5mA @ 0.2 A~1 A dc

±0.5% @ 1 A~20 A dc

Resolution1mA
Distortion<0.1% Guar. / <0.05%Typ.
Frequency Output
Range5~1000 Hz, 3KHz transient output
Accuracy<1ppm @ 5~65 Hz
<10ppm @ 65~450 Hz
<20ppm @ 450~1000 Hz
Resolution0.001 Hz
Phase Output
Range-360°~360°
Accuracy<0.05° Typ. / <0.1° Guar.
Resolution0.001°
Aux. DC Voltage Source (Battery simulator)
Range0~310V @ 124W max
Binary Input
Quantity8pairs
Input Characteristics0~400Vdc / Potential free
Time Resolution<0.1ms
Max. Measuring TimeInfinite
Debounce Time0~25ms
Binary Output
Quantity

4pairs NO relay contacts

(4paris semiconductors output optional)

TypePotential free, software controlled
Break Capacity

Vmax:300Vac Imax:4A Pmax:1000VA

Vmax:300Vdc Imax:4A Pmax:300W

Synchronization
Synchronization ModeGPS, SMA type antenna connector
Harmonic
Superimposed Numbers2~20times
Power supply & Environment
Nominal Input Voltage110/220/230Vac preselection
Permissible Input Voltage

+/-20%, Max 264Vac

Self-protect and alarm if input voltage out of range

Nominal Frequency50/60Hz
Permissible Frequency45Hz~65Hz
Power Consumption1500 VA max
Connection TypeStandard AC socket 60320
Operating Temperature-10℃~55℃
Storage Temperature-25℃~70℃
Humidity<95%RH, non-condensing
Others
PC ConnectionRJ45 Ethernet, 10/100/1000M
Grounding Terminal4mm banana socket
Weight20 Kg
Dimensions(W x D x H)480×320×160(mm)
 

 

Additional Information (Optional Modules)

Low-Level outputs
Quantity13 Channels, phoenix male type
Voltage Outputs RangeAC 0~8V, DC 0~10V
Current Outputs RangeNominal 2mA, 10mA max transient
Output Power≥0.5VA
Accuracy

(0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar.

(0.8~8 Vrms): <0.02% Typ. / <0.05% Guar.

Resolution0.25mV
Energy Meter Calibration
Sensor UsageMechanical meters / Electronic meters
Sensor OutputHigh lever:>4.5V, Low level:<0.2V
Pulse Input1 pulse input port
Pulse Range500KHz pulse input Max.
Pulse Output1 Transistor output
 

 

 

Hot Products

3.8kg, 6x20A & 4x300V, high current up to 60A High precision class 0.05 Supports IEC61850 SV/GOOSE, ...
Universal Relay Test Applications 3x35A & 4x310V independent high burden output channels Lightweight...
Universal Relay Test Applications 6x35A & 4x310V independent high burden output channels Lightweight...
System Description K68i Relay Tester is new mode of All-in-One testing systems on relay protection ...
Able of what K31 series can test Items ANSI® No. IEC61850 numerical IEDs relay & merge unit Distance ...
Able of what K68 series can test Items ANSI® No. Distance protection relay 21 Synchronising or ...