High performance Flame Retardant Cable Tinned copper Conductor BS7629 1

 

 

APPLICATION
Hard Skin Standard Fire Resistant Cables for use primarily in fire detection, fire alarm, voice alarm, and emergency lighting circuits. These cables are designed to continue to operate for a period of time in a fire situation.
‘Enhanced grade’ fire resistance is recommended for systems, in particular building types, in which cables might need to operate correctly during a fire for periods in excess of those normally required for single phase evacuation of a building.

 

 

CONSTRUCTION
Conductor

1.5mm2- 2.5mm2: Class 1 solid conductor according to BS EN 60228
4mm2: Class 2 stranded conductor according to BS EN 60228

 

 

Insulation
Mica/Glass fire resistant tape covered by high performance fire resistant silicone rubber

 

 

Overall Screen
AL/PET (Aluminium/Polyester Tape)

 

 

Circuit Protective Conductor

Tinned copper

 

 

Outer Sheath
LSZH (Low Smoke Zero Halogen)

 

 

STANDARDS
BS 5839-1:2013 Clause 26.2e, BS EN 50200:2015 (PH 30 - PH 60 - PH 120), BS 6387:2013, BS 7629-1, IEC 60331 BS 6387 (cat. C-W-Z), BS EN 50200 (class PH120), BS EN 50200, BS 8434-2 (120 min), BS EN 60332-1-2, BSEN 60332-3-24 cat. C, BS EN 60754-1, BS EN 60754-2, BS
EN 61034-2, BS 5266-1, BS 8519 We supply LPCB certified products

 

 

We supply LPCB Certified products
The electrical and dimensional properties of this product are measured by the Technical and Quality Assurance department at the  Cables laboratory. Cable performance in respect of conductor resistance, construction quality (workmanship), dimensional consistency, and other parameters are verified to published standards and approved product drawings. Conformance to RoHS (Restriction of the use of Hazardous Substances) is determined and confirmed

 

 

CHARACTERISTICS
Voltage Rating
300/500V

 

 

Operating Temperature
-40°C to +90°C

 

 

Minimum Bending Radius
6 x overall diameter

 

 

Core Identification

2 cores: Blue Brown + Bare Earth

3 cores: Brown Black Grey + Bare Earth

4 cores: Blue Brown Black Grey + Bare Earth

 

 

Outer Sheath Colour
Red

Hot Products

Copper Core Low Smoke Zero Halogen Wire Four Core XLPE Insulated Ls0h Cable APPLICATION BS 5308 ...
BS 5308 Low Smoke Zero Halogen Cable Silicone Class 1 Solid Copper Conductor APPLICATION BS 5308 ...
Four Core Flame Retardant Cable 30 Minutes 1 Hour 2 Hour Fire Rated Cable We supply a full range of ...
LSZH Flame Retardant And Fire Resistant Cables Three Core For Underground APPLICATION Hard Skin ...
High performance Flame Retardant Cable Tinned copper Conductor BS7629 1 APPLICATION Hard Skin ...
Steel Wire Armour Fire Resistant Low Smoke Cables XLPE Insulation BS 7846 APPLICATION Firetec Impact ...