I. Brief

1.1 Name and Model: 12kV pad mounted metering unit PMY6-12, combined transformer JLSZXW6-12

1.2 Description

This metering unit is for outdoor installation, in power distribution system upto 12kV(Um) for metering and measuring, with a factory-assembled three-phase combined transformer of CT, VT inside. Three-phase voltage transformers’ wiring method Y-Y star connection, and current transformer is optional, eg. two-phase CT, three-phase CT. Panel type is metal-clad, made from galvanized steel, stainless steel, or alloy aluminum. Enclosure surface is painted with color and protection layer for resistance to acid and alkali corrosion, and UV radiation. It is applied to connecting outdoor underground cable with utility company power system. The metering unit has two compartments, including a factory-assembled low voltage compartment for energy meter, and test terminal block of combined transformers. End customers can install a suitable energy meter in the compartment.

1.3 Electrical data

No.itemunitsspecification
  1.  

Highest voltage for
equipment Um (r.m.s.)

 

kV12
  1.  
rated frequencyHz50, 60 or 50/60
  1.  

Rated lightning impulse
withstand voltage (peak)

 

kV75, 95
  1.  

Rated power-frequency
withstand voltage on primary

 

kV28
  1.  

Rated power-frequency
withstand voltage on secondary

 

kV3
  1.  
Number of CTs and VTspcs3VT+3CT or 2CT+3VT
  1.  
Standard/IEC 61869-1:2007 | IEC 61869-2:2012 IEC 61869-3:2011 | IEC 61869-4:2013
 

II. Application

Pad mounted primary metering unit can meet the latest standards nationally and globally. It is connected with power distribution net three-phase cable for power metering management and automation system, to get primary metering more accurately. Thus, utility company will account power loss more effectively and increase revenue.

 

III. Features

1. Metering unit consists of 4 compartments, including cable entry compartment, cable outgoing compartment, MV combined transformer compartment, and energy meter compartment. Adjustable feet (supporting frame) structure enables this metering unit unaffected by weather conditions, such as wind/flood/snow. Outdoor pad mounted design is convenient and fast;
2. Metering unit has been factory-assembled as a complete unit, door opening sensor for safety operation, lock sealable for anti-theft electricity and unwanted open;
3. Enclosure made from stainless steel or equivalent material, such as low carbon steel. Hermetically sealed design is waterproof. Enclosure surface coating power is anti-corrosion layer, for resistance to acid and alkali corrosion, and UV radiation;
4. Touch-proof type, medium voltage combined transformer is encapsulated in casting epoxy resin with a metallic coating. No need insulation between combined transformer and compartment. This compact design vessel only needs 1/2 space compared with air insulated metering unit. No oil and no need maintenance, safety operation and environmentally friendly;
5. Primary side bushing connected through set of separable Tee connector, which meets IEC 50810/IEC 50181 interface C, or A, B.

 

IV. Technical data

Current transformer specifications

 

NoItemspecification
  1.  
Rated primary current5A up to 600A
  1.  
Rated secondary current5A, 1A
  1.  
Rated Continuous Thermal Current120%, 125%, 150%, 200% etc.
  1.  
Rated Short time current (Ith) (thermal 1 second)80xIpr, 100xIpr
  1.  
Rated Dynamic Current (Idyn)2.5xIth
  1.  
Rated Output(VA)12.5, 15, 20
  1.  
Accuracy Class0.2S, 0.2, 0.5S, 0.5, 1 Metering
  1.  
Instrument Security Factor (FS)5, 10
  1.  
Applicable StandardIEC: 61869-1&2
Voltage transformer specifications
NoItemspecification
  1.  
Rated primary voltage(V)10000/√3, 11000/√3
  1.  
Rated secondary voltage(V)100/√3, 110/√3
  1.  
Rated Voltage Factor

1.2/Continuous

1.5/30s, 1.9/30s, 1.9/8h

  1.  
Standard connectionY-Y (star connection)
  1.  
Rated Output(VA)15, 20, 25, 30, 50, 75
  1.  
Accuracy Class0.2, 0.5, 1, 3 metering
  1.  
Thermal burden(VA)300, 400
  1.  
Applicable StandardIEC: 61869-1&3

Other specifications are available as per clients’ requests

 

V. Dimensional drawing and wiring

 

dimensional drawing


wiring

 

VI. Special requirements

Other specifications are available as per clients’ requests.

Hot Products

1. Product introduction: 1.1 Product type name and model: Install the metering box OMV-12, JLSZVW-12 ...
1. Product introduction: 1.1 Product type name and model: Install the metering box OMV-36, JLSZVW-36 ...
1. Product introduction: 1.1 Product type name and model: Install the metering box OMY-12, JLSZYW-12 ...
1.Product Introduction 1.1 Product Type Model: 17.5kV MV Overhead Pole Mounted Metal Casing Dry type ...
I. Brief 1.1 Name and Model: 12kV pad mounted metering unit PMY6-12, combined transformer JLSZXW6-12 ...
I. Brief 1.1 Name and Model: 12kV pad mounted metering unit PMY5-12, combined transformer JLSZXW5-12 ...