Home Companies GuangDong Heng AnShun Electrical Power Equipment Service Co., Ltd.

Automatically Operated High Voltage Electrical Isolator 8 Level Earthquake Intensity

GuangDong Heng AnShun Electrical Power Equipment Service Co., Ltd.

Contact Us

[China] country

Trade Verify

Contact name:Sherlin

Inquir Now

GuangDong Heng AnShun Electrical Power Equipment Service Co., Ltd.

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

Automatically Operated High Voltage Electrical Isolator 8 Level Earthquake Intensity

Country/Region china
Categories Cap Making Machinery Parts
InquireNow

Product Details

Automatically Operated High Voltage Electrical Isolator Safety Operated Of High Voltage Breaking Ceramic Hookstick

 

 

Product Description:


 

High voltage electrical isolator is a type of electrical switch used to isolate a section of an overhead power transmission line for maintenance or repair. It is typically used in high voltage electrical systems, such as those used by power utilities to transmit electricity over long distances.

The switch is mounted on an overhead structure, such as a transmission tower or pole, and is designed to withstand the harsh environmental conditions encountered in outdoor electrical systems. It features a vertical, or up-and-down, motion to engage or disengage the switch contacts, which are typically made of copper or other conductive materials.

The electrical isolator is designed to provide a visible break in the transmission line, allowing maintenance personnel to safely work on the line without risk of electrocution or damage to equipment. It is often used in conjunction with other safety devices, such as grounding switches and surge arrestors, to protect the electrical system and the people working on it.

Overall, the high voltage electrical isolator is an important component of modern power transmission systems, ensuring reliable and safe operation of the electrical grid.

 

 

 

Application:


 

1.Maintenance and Repair: The Loadbuster Electrical Isolator is commonly used to isolate and ground electrical distribution lines for maintenance and repair activities. It allows maintenance personnel to work safely on energized equipment without the risk of electrocution.

2.Emergency Response: The Loadbuster Electrical Isolator can be used in emergency situations, such as power outages or natural disasters, to isolate and ground electrical distribution lines and restore power safely.

3.Switching Operations: The Loadbuster Electrical Isolator can be used to open or close switches and perform other switching operations on electrical distribution lines.

 

 

 

Safety Tips:


 

1.Always wear appropriate personal protective equipment (PPE) such as gloves, safety glasses, and flame-resistant clothing.

Before working on the switch, ensure that the power supply is turned off, and the switch is properly grounded.

2.Follow the manufacturer's instructions for operating the switch, and do not attempt to bypass safety features or use the switch for purposes other than its intended use.

3.When working on the switch, use insulated tools and equipment to prevent electric shock.

4.Avoid touching any conductive parts of the switch and keep a safe distance from the switch when it is in operation.

5.Never attempt to repair or modify the switch yourself unless you are a qualified and trained professional.

6.Keep the area around the switch clean and free of debris that may interfere with its operation.

7.Regularly inspect the switch for signs of wear or damage, and replace any damaged or worn parts as soon as possible.

8.Only authorized personnel should be allowed to operate or perform maintenance on the switch.

9.In case of an emergency, follow established emergency procedures and shut off power to the switch immediately.

 

 

 

Operation:


 

1.Closing the Switch: When the switch is closed, the two conductive parts of the circuit are brought into contact with each other, allowing electrical current to flow through the circuit.

2.Opening the Switch: When the switch is opened, an air gap is created between the two conductive parts of the circuit, effectively isolating the section from the rest of the system. This is typically done to allow maintenance, repair, or testing work to be carried out safely.

3.Grounding the Circuit: Before any work can be carried out on the isolated section of the circuit, it is important to ground the circuit to prevent any residual electrical charge from building up. This is typically done using an earth switch or grounding electrode.

 

 

 

Structure:


 

This product is composed of base (plate), post insulator, conductive part and interlock device. One end of the knife is installed on the dynamic contact knife head through bolts, and the other end of the knife is separately connected with the static contact head, and each side is maintained in a good contact state by the pressure of the compression spring. Each knife is slot-shaped type, which not only increases the heat dissipation surface of the knife, but also conducive to reducing the temperature rise, and improve the mechanical strength of the knife, making the dynamic thermal stability against short circuit. The interlocking parts installed at the non-rotating end of the contact knife and the static locking hook on the static contact constitute the opening locking device, which is self-locking when the brake is closed, so that the brake knife will not fall off by itself due to its own weight or the action of electric power, resulting in the opening of the brake without cause.

 

 

 

Technical Parameters:


 

Serial No.ParameterUnitData
1Rated VoltagekV12
2Rated CurrentModel No.(H)GW9-12(W)/630-20A630
(H)GW9-12(W)/1000-201000
(H)GW9-12(W)/1250-31.51250
34s Short-time withstanding currentModel No.(H)GW9-12(W)/630-20kA50
(H)GW9-12(W)/1000-2050
(H)GW9-12(W)/1250-31.580
4Rated Insulation LevelLightning surge withstand voltage(peak)Polar-to-Earth
(Positive & Negative)
kV75
Interfracture
(Positive & Negative)
85
Industrial frequency withstand voltage
(1 min)
(Effective value)
Dry Test/Wet TestPolar-to-Earth42(Dry)
34(Wet)
Interfracture48(Dry)
48(Dry)
48(Dry)
40(Wet)
5Main Circuit Resistanceμ Ω630
1000
1250
6Mechanical Life Timetimes50
50
80

 

 

 

Hot Products

Outdoor Hookstick Switch 1 Pole Automatic Controlled Electrical Isolator Installed For Overhead ...
Industrial High Voltage Electrical Isolator Of New GW9 Series Reset Automatically Safety Operated ...
Industrial Powerful High Voltage Electrical Isolator With Thickened Stainless Steel More Stable For ...
Easy Operation High Voltge Electrical Isolator Outdoor Used AC Power Electrical Loadbuster ...
Automatically Operated High Voltage Electrical Isolator Safety Operated Of High Voltage Breaking ...
AC Power High Voltage Electrical Isolator Made By Heightened Ceramic Isolator Single Phase Hookstick ...