ZW20-12(F) Vacuum Electrical Sectionlizer Manually/Automatically Used With Smart Controller For Distribution System
Product Description:
ZW20-12(F) vacuum circuit breaker is three phase AC 50Hz outdoor HV switchgear is mainly used for rural and urban 10 kV outdoor distribution network, as a separate and combined load current, overload current, short circuit current and other similar places.
Its whole structure is a three-phase common box type, which is composed of an operating mechanism, a conductive circuit, an insulating system, a sealing element and a shell.
And it is supporting the corresponding intelligent remote terminals to meet the application needs of distribution automation.
Characteristics of the controller:
1.Multiple Communication Options: The ZW20-12 circuit breaker
offers flexible communication options, including a 485/232
communication interface for local monitoring and control. It can
also support long-distance monitoring through fiber optics or
wireless communication, providing versatile connectivity solutions
to meet different system requirements.
2.Automatic Acceleration to Trip: In the event of a permanent
fault, the circuit breaker automatically accelerates to trip. This
feature helps ensure a swift and reliable response to fault
conditions, minimizing potential damage to the electrical system
and enhancing overall system safety.
3.Remote Control and Manual Reclosing with Acceleration to Trip:
The ZW20-12 circuit breaker supports both remote control and manual
reclosing operations. In cases where the line is repaired and power
is restored but the grounding knife switch is accidentally left in
place, the circuit breaker accelerates to trip, providing an
additional safety measure to prevent potential hazards.
4.Adjustable Reclosing Delay: The delay time for reclosing can be
adjusted for all three reclosing attempts. This adjustable feature
allows for fine-tuning the reclosing timing based on specific
system requirements, optimizing the coordination with other
protective devices and improving system reliability.
5.Anti-Reclosing Functionality and False Operation Prevention: The
trip/reclosing circuit of the ZW20-12 circuit breaker is designed
to prevent false operations. It incorporates mechanisms and
safeguards to minimize the risk of unintended reclosing, ensuring
that the circuit breaker operates only when intended and avoiding
potentially hazardous scenarios.
6.Fault Differentiation with Zero-Sequence Current: The circuit
breaker utilizes zero-sequence current analysis to differentiate
between faults occurring inside and outside the protected zone.
This capability helps localize and identify faults accurately,
enabling efficient fault isolation and reducing downtime in the
electrical system.
7.Design for Remote Control False Operation Prevention: The remote
control trip/reclosing feature of the circuit breaker is designed
to prevent false operations. Specific measures and safeguards are
implemented to minimize the risk of unintended tripping or
reclosing caused by external factors, ensuring reliable and
accurate remote control functionality.
Feature:
1.Vacuum Interruption Technology: The ZW20-12 circuit breaker
utilizes vacuum interrupters as the arc extinguishing medium.
Vacuum interrupters are highly effective in quenching arcs and
provide excellent dielectric strength, ensuring reliable
interruption of high voltage currents.
2.Outdoor Application: This circuit breaker is specifically
designed for outdoor installation, making it suitable for use in
substations, distribution networks, and other outdoor electrical
systems. It is built to withstand harsh environmental conditions,
including temperature variations, humidity, and exposure to dust,
rain, and UV radiation.
3.High Voltage Rating: The ZW20-12 circuit breaker is designed for
high voltage applications, with a rated voltage of 12 kilovolts
(kV). It can handle electrical systems operating at this voltage
level.
4.Compact Design: The circuit breaker features a compact design,
allowing for easier installation and integration into outdoor
switchgear or substation arrangements. The compact size also
facilitates space-saving and efficient use of available
installation area.
5.Reliable Operation: The ZW20-12 circuit breaker is engineered for
reliable operation. It incorporates high-quality materials,
precision-engineered components, and advanced mechanisms to ensure
stable and efficient switching operations, minimizing the risk of
faults or failures.
6.Safety Features: The circuit breaker is equipped with safety
features to enhance operator and system safety. These may include
interlocking mechanisms to prevent incorrect operation, mechanical
and electrical indicators to provide status information, and safety
shutters to prevent accidental contact with live parts.
7.Remote Control and Monitoring: Some versions of the ZW20-12
circuit breaker may support remote control and monitoring
capabilities. This allows for convenient operation and monitoring
of the circuit breaker from a central control room or through a
supervisory control and data acquisition (SCADA) system, enhancing
system management and maintenance.
Application
1.Substations: The ZW20-12 circuit breaker is often employed in
outdoor substations as a part of the primary distribution system.
It is used to protect and control electrical equipment such as
transformers, generators, and busbars.
2.Distribution Networks: This circuit breaker is suitable for
outdoor distribution networks where high voltage power is
distributed to multiple locations. It helps to ensure reliable and
safe operation by interrupting fault currents and isolating faulty
sections of the network.
3.Industrial Facilities: The ZW20-12 circuit breaker is utilized in
outdoor high voltage systems found in industrial facilities such as
factories, manufacturing plants, and mining operations. It provides
protection for critical electrical equipment and ensures the
continuity of power supply.
4.Renewable Energy Installations: In outdoor renewable energy
installations like wind farms or solar power plants, the ZW20-12
circuit breaker is employed to protect the electrical
infrastructure and switch the power generated by renewable sources.
5.Railways: This circuit breaker is used in outdoor high voltage
systems associated with railway electrification. It ensures the
safe and reliable supply of power to railway systems, including
overhead catenary systems and traction substations.
6.Oil and Gas Industry: The ZW20-12 circuit breaker finds
application in outdoor high voltage systems within the oil and gas
industry. It is used to protect electrical equipment and control
power distribution in offshore platforms, refineries, and pumping
stations.
7.Infrastructure Projects: The ZW20-12 circuit breaker is suitable
for various outdoor infrastructure projects such as airports,
seaports, and power transmission lines. It plays a crucial role in
protecting critical infrastructure and ensuring uninterrupted power
supply.
Technical Parameters:
Serial No. | Parameter | Unit | Data | ||||||||
1 | Rated voltage | kV | 12 | ||||||||
2 | Insulation level of Fracture | Working Frequency(Dry Test/Wet Test) | 48 | ||||||||
Voltage of Lightning Shock Test (Peak) | 85 | ||||||||||
3 | Level of Insulation to ground/phase to phase | Working Frequency | Dry Test | 42 | |||||||
Wet Test | 34 | ||||||||||
Voltage of Lightning Shock Test (Peak) | 75 | ||||||||||
4 | Rated Current | A | 630, 1250 | ||||||||
5 | Rated short-circuit breaking current | kA | 16, 20, 25 | ||||||||
6 | Rated short-circuit breaking current breaking times | times | 30 | ||||||||
7 | Rated short-time withstanding current | kA | 16, 20, 25 | ||||||||
8 | Rated short-circuit duration | S | 4 | ||||||||
9 | Rated short-circuit closing current (peak) | kA | 40, 50, 63 | ||||||||
10 | Rated peak withstanding current | kA | 40, 50, 63 | ||||||||
11 | Mechanical lifetime | times | over 1000 | ||||||||
12 | Opening rated current | 10000 | |||||||||
13 | Net Weight | kg | 180 |
Technical Parameter of Controller:
Serial No. | Parameter | Data | ||||||||
1 | Woking input voltage | AC220V | ||||||||
2 | Input working frequency | 50Hz | ||||||||
3 | Allowable voltage fluctuation range for input voltage | ±20% | ||||||||
4 | Total power consumption of the device | <10W | ||||||||
5 | Sampling value of phase current input | 60-600A | ||||||||
6 | Low voltage operation threshold | 10-140V | ||||||||
7 | Allowable sampling error for power input value | ±5% | ||||||||
8 | Overcurrent protection delay time value | 0.1-0.3s | ||||||||
9 | Setting value for zero-sequence current | 0.2-6A | ||||||||
10 | Grounding action delay time | 0-1200s | ||||||||