Wuhan Huaying Electric Power Tech & Science Co., Ltd |
|
220V 50Hz Current Transformer Test Set For Testing Turn Ratio , Excitation Parameters
2. Equipment Description:
HYVA-402 can finish:
CT/PT volt-ampere characteristic curve test,
CT/PT Polarity test,
CT/PT Transformation ratio test,
automatically calculate error curve of any CT point.
3.Technical Specification:
1 The instrument is easy to operate.Complete computerize device and high performance CPU,no need manual work,it finishes test automatically,which prevent person from high voltage circuit.
2 Large output. Maximum output voltage of volt-ampere characteristic test reaches to 1000V,Maximum output current of transformation ratio test is 600A,output capacity of internal voltage regulating machine is 5KVA.
3 Optional accessory includes external join to voltage raising machine ,current raising machine and voltage regulating machine.Maximum voltage of external voltage raising machine is 2000V,3A;Maximum current of external current raising machine is 1000A;Maximum output of external voltage regulating machine is 1500V,20A.You can have a CT test of reach up to 500KV,1A when using external voltage raising machine.
4 320*240 Large screen,it can display volt-ampere characteristic curve directly when the test is finished.It can print curve and result anytime with micro-printers of the tester.
5 Adapt rotating mouth,easy operation and durable use.
6 Flash Ram inside,prevent data losing from power off.
7 RS232 communication interface,make sure connection of the instrument and PC,triers can control the test and unload the test data through PC.
8 AC220V and AC380V power supply