Full-automatic Transformer Integrated Test Bench , Power Transformer Comprehensive Test Systems

 

I. Products Description and Application 

 

Before and after the manufacture or maintenance of the power transformer, necessary rutine quality inspection and test items are required.

Power Transformer Comprehensive Test Systems are designed and used for the above test purpose. According to the different test items requirements of the customer's order, it adopts a comprehensive and modular software with PLC computer and intergrate the additional current meter ,voltage meter and power meter to be one-body type test bench ,greatly improved test efficiency ,applicabilityand test accuracy. It can automaticcly form and save test report , and print the report by outside printer.

The test systems can finsh the test items including as following :

 

1.1 Main test items inside the system

  • Transformer no-load characteristic test;
  • Transformer load characteristic test;
  • Power frequency AC voltage withstand test;
  • three doubleing frequency induced withstand voltage test;
  • Transformer harmonic  test;
  • Transformer DC resistance test;
  • Transformer ratio, group, error test;
  • Transformer temperature rise tests.

 

1.2 Assisted test items outside the system

  • Transformer insulation resistance, absorption ratio, polarization index test;
  • Transformer insulating oil analysis system;
  • Transformer dielectric loss test;
  • Partial discharge tests;
  • Environmental temperature and humidity testing.

 

​1.3 Customization ability to test power transformer

 

  • Capacity :       360000kVA and below
  • Voltage level : 500kV,330kV,220kV,110kV, 35kV/10kV, single, three-phase power transformers  
  • Unversal test accuracy and range as following table 

 

Item

 

Scope of measurement

 

Relative error

 

Voltage

0.1-600V

 

±(0.2% reading + 0.1% range)

 

Current

0.1-200A

 

±(0.2% reading + 0.1% range)

 

Power

U*I

 

±(0.2% reading + 0.1% range)

 

Power factor

0.1-0.9999

 

±3 figures

 

Power supply

AC220V±10% 50Hz±2%

 

Operating condition

 

Working temperature range 0-40℃ Relative humidity 30%-90%

 

Outline dimension

 

Customization

 

Weight

 

Customization

 

 

II. Test system includes three main parts  

 

Transformer integrated test system monitoring stations(or names Monitoring and sampling cabinet);

Transformer integrated test system controlling cabinet (or names Auxiliary control cabinet);

Transformer integrated test system operating platform(or names Test bench);

 

III. Universal Structure and function features

  • The system adopts computer auto operation and retains the manual operation function, it can use the mouse or touch screen to complete the test, the test data can be automatically uploaded to the test report after finish testing, you can automatically call out the original test data through just entering the data number .
  • Automatically select the high and low voltage current and voltage gear after input transformer basic parameters (capacity, high and low voltage side) by the keyboard;
  • Automatic switching gear (no NEED manual button), and automatic switching;
  • Automatic lifting regulator, and automatic speed control, to the rated current or voltage automatically stops;
  • Automatic abnormal current, voltage protection, and alarm instructions;
  • Automatic data acquisition, and automatically save the data, automatically restore the initial state machine;
  • Automatic printing factory test report.
  • All monitoring parameters and vector diagram are displayed on the same screen according to international standards
  • Adopt high accuracy power analyzer to ensure measuring accuracy. The power analyzer is developed by our company and has been successfully developed by ourselves and worked in the Chinese national transformer quality inspection center for two years.
  • The System has software ,hardware,system interlocking and other multiple protection, adopts split-body design, separate design on the control circuit part of primary and secondary ;
  • Voltage regulator adopts variable-frequency technology to realize arbitrarily adjust on the motor speed ,Greatly improving the work efficiency and test data accuracy.
  • The system can preform 31 times harmonic analysis test. .

 

VI.Application of Model FKBT-III-250KVA (for example)

 

4.1.The system is applied for the power transformer test , tested transformer spec. is as following :

  • Tested capacity :2500KVA and below
  • HV side rated voltage: 35KV,22KV
  • LV side rated voltage: 0.4~6KV
  • The max impedance level : no more than 8%

 

 

4.2 The system has the following test functions: 

 

SN.Test itemsTest in the buyers sideTest in the customers side
1No load feature test for power transformer
2Load loss feature test for power transformer
3Power frequency voltage withstand test for power transformer
4Three doubling frequency Induced voltage withstand test for power transformer
5Winding Ratio and polarity test for power transformer winding
6DC resistance test for power transformer winding
7Temperature rise test for power transformer

 

 

4.3 Reference Standard

 

GB 1094.1——1996Power transformer part 1 :general
GB 1094.2——1996Power transformer part 2 :temperature rise
GB 1094.3——1996Power transformer part 3:Insulation level, insulation test and outer insulating air gap
GB/T 1094.10——2003Power transformer Sound level measurement
GB/T 6451——1999Three-phase oil-immersed power transformer technical parameters and requirements
GB 1094.11——2007Dry-type power transformer
GB/T 10228--2008Dry-type power transformer technical parameters and requirements
GB/T 15164——1994Oil-immersed power transformer load guideline
GB/T 507——2002Insulating oil breakdown voltage measurement
IEC60076-1 ~5Power transformer
IEC60726Dry-type power transformer

 

 

4.4. The configuration and the supply scope for export 

Case No.Components Name &Specification in the wooden caseQtyPackage

N.W.

( kgs)

G. W.

(kgs)

L*W*H

(mm)

Volume

(m3)

8-1

Power Transformer Integrated Test Bench ,model :FKBT-III-250KVA

Including host machine,necessary components , wires, test accessories and so on

1pcsWooden case110012502500*1080*14603.942
8-2

LV Auxiliary control console ,

model FKBT-III ,including Industrial Control Computer With professional testing software and part test cables

1pcsWooden case6507001100*1050*24302.842
8-3HV Auxiliary control console and HV accuracy CT &PT,including part test cables1pcsWooden case7007501300*1130*24303.614
8-4

Induction type electric voltage regulator (Three phase type),

model TSJA-250kVA

1pcsWooden case151016001265*1265*17002.721
8-5Intermediate frequency generating unit ,model FKBF-40kVA1pcsWooden case6206501830*600*9000.989
8-6Put-line cabinet for Temperature rise test and Environmental temperature inspecting tester and Temperature sampling probe1pcsWooden case165200550*580*8100.259
8-7

Intermediate Test Transformer

(three phase type),

model :YDJ-250kVA/2;3;6;12kV/0.6kV

1pcsWooden case290031501910*1850*20007.067
8-8

Oil-immersed test transformer set

CQSB(j)-40KVA/50.75.100KV

1pcsWooden case5506001120*860*16101.551
TOTAL:8cases8235kgs8950kgs 22.985m3

 

 

 

 

 

 

 

 

 

Hot Products

Power Transformer Three Channel DC Resistance Tester ,Three Phase 10A Test Current Output I. ...
Power Transformer Ratio and Polarity Tester , Transformer Windi Ratio Tester , Laboratory Equipment ...
Transformer Capacitance & Tan Delta Tester , Automatic Tan Delta Tester , Dielectric Loss & ...
Induced Voltage Withstand Test Set For Power Transformer , Triple Frequency Power Generation Group I...
Full-automatic Transformer Integrated Test Bench , Power Transformer Comprehensive Test Systems I. ...
PD Free AC Withstand Voltage Test Systems With Cylinder Type Transformer , Partial Discharge ...