Home Companies Guangdong Fullde Electrical Technology Co., Ltd

AC415V 35KW Electrical Testing Load Bank for Generator Continuous Duty Cycle

Guangdong Fullde Electrical Technology Co., Ltd
Active Member

Contact Us

[China] country

Address: Baisha 3rd Village Industrial Area, Humen Town, Dongguan City, Guangdong Province, China

Contact name:Alina

Inquir Now

Guangdong Fullde Electrical Technology Co., Ltd

AC415V 35KW Electrical Testing Load Bank for Generator Continuous Duty Cycle

Country/Region china
City & Province dongguan guangdong
Categories Generator Parts & Accessories
InquireNow

Product Details

Fullde AC415V 35KW Power Factor 1.0 Electrical Testing Load Bank for Generator

 

1. Technical standards
FULLDE provide the equipment and accessories which meet the following standards, but not limited to the following criteria:
1) National standards: GB/T 14048.1-2000
Low-voltage switchgear and control equipment


2) National standards: GB/T 7251-2005
Low-voltage complete switch and control equipment

 

3) Industry standard: JB/T 9696.1-1999
Low-voltage complete switch and control equipment with terminal row


4) IEC 60034 Rotating Electrical Machines


5) IEC 60364 Low Voltage Electrical Installations


6) IEC 60664 Insulation Coordination for equipment within low-voltage systems


7) IEC 60529 Degrees of protection provided by enclosures (IP Code)


8) NFPA 110 Standard for Emergency and Standby Power Systems

 

2. Conditions
1) Ambient temperature: - 25 ~ 55 ℃


2) The relative humidity: average less than 90%


3) Altitude: ≤2500m


4) The installation conditions: without corrosive or flammable gas, water vapor etc some other
obvious pollution, and without violent vibration.

 

3. Equipment technical parameter

 

System CompositionResistor, air cooling, the electric parameters testing, control panel
Resistor ElementSpecial alloy resistance, high temperature resistance, corrosion resistance, high precision, long service life, resistance tolerance is ±5%;
ConnectionThe three-phase four wire system, star connection method, copper;
ControlContactor
Control Voltage3P4W, 415VAC,50Hz;
Dimension(mm)750*850*1300mm;
Weightabout 100KG
Load element typePure resistive
ControlLocal manual control;
Load Tolerance±5%;
Way of WorkingContinuous working;
Cooling typeForce air cooling;
Insulation gradeF;
Protection

1. Emergency Stop: User can press the emergency stop button in the panel to unload immediately when the load bank is abnormal while working;

2. Short Circuit Protection: Fuse could avoids damage to equipment when short circuit or current overload;

3. Fan Air Quantity Protection: when the wind is insufficient, the machine will unload and give alarm;

Protection Buttonthere are protection button both in local control and remote control can be switched off when false alarm or for special requirements.
Protection GradeIP23;
TransportationRings on the top or caster wheels;

 

4. Control Panel Introduction

 

 

Hot Products

FULLDE 200Kw Resistive Portable Loadbank Color Grey for Generator Testing Technical Parameters ...
FULLDE 250Kva 400V Stainless Steel Load Banks for Generator Rental Introduction of load bank: Power ...
Fullde 80kw Resistive 32VDC Load Bank used for generator Test Introduction: This unit specially ...
100KW 75Kvar 380VAC RLC Dry Load Bank for Generator Testing Introduction: Power generator intelligen...
Fullde AC415V 35KW Power Factor 1.0 Electrical Testing Load Bank for Generator 1. Technical ...
Fullde 1800KW Grey Color Load Bank Test Generator for Middle East 1. Verification Testing a) ...