The electric heating steam boiler adopts the separation mode of the furnace body electric control cabinet, which avoids the influence of the service life of the electrical components due to heat aging. Heater choose ceramic electric heating tube, low surface load, long service life; With a single small flange connection, easy maintenance; Its normal service life is about 20,000 hours, the thermal efficiency is nearly 99%, the operation is quiet, clean, in line with the requirements of environmental protection, will not emit NOx (nitrogen oxides) to the atmosphere; The operation part adopts PLC control system, all free operation button, all free indicator light, touch screen panel, Chinese and English display, man-machine dialogue, operation authorization, real-time information, automatic page turning.
1, the use of advanced computer boiler controller PLC microcomputer
programmable control and display screen, through the man-machine
interface to set its working pressure, working time and other
functions, can display equipment status operating parameters and
fault alarm; It has the advantages of reliable performance, high
degree of automation and easy to use.
2, the electrical components have CE and CCC demonstration mark,
the selection of domestic and foreign high-quality products, and
the test furnace aging test, to ensure the long-term normal
operation of the boiler.
3, the high-power electric steam boiler adopts the separation of
the furnace body and the control cabinet, which can be used in
parallel with a single or multiple sets to avoid the use of
electrical components affected by heat.
Model | WDR0.5 | WDR1 | WDR1.5 | WDR2 | WDR3 | WDR4 | WDR6 |
Rated steam (t/h) |
0.5 |
1 |
1.5 |
2 |
3 |
4 |
6 |
Electric power (KW) |
375 |
750 |
1050 |
1500 |
2250 |
3000 |
4500 |
Rated pressure (Mpa) |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
0.7/1.0/1.25 |
Rated steam Temperature(℃) |
170/184/194 |
170/184/194 |
170/184/194 |
170/184/194 |
170/184/194 |
170/184/194 |
170/184/194 |
Heat Efficiency (%) |
99 | ||||||
Size(mm) | 2666*1536*1566 | 3000*1400*1650 | 3500*1600*1750 | 4000*1700*1950 | 4312*2124*2242 | 4380*2400*2662 | 4908*2671*3390 |
Reference weight (kg) |
1263 |
2100 |
2600 |
3100 |
5450 |
5203 |
6600 |
1, power abnormal protection function: boiler immediately stop
operation.
2, leakage protection function: the control system detects leakage
of electric heating elements, will automatically cut off the power
supply.
3, water shortage protection: when the boiler is short of water,
the heating pipe control circuit is cut off in time to prevent the
heating pipe from dry burning damage, and the controller issues a
water shortage alarm indication.
4, power abnormal protection function: boiler immediately stop
operation.