Home Companies Dongguan Tianrui Electronics Co., Ltd

HD Series Electromagnetic Overload Protector Hydromagnetic Hydraulic Magnetic Circuit Breaker 32V 48V 60V 80V DC

Dongguan Tianrui Electronics Co., Ltd

Contact Us

[China] country

Trade Verify

Address: Building C, Xinmeijia Science and Technology Park, Chashan

Contact name:Andy Wu

Inquir Now

Dongguan Tianrui Electronics Co., Ltd

Verified Suppliers
  • Trust
    Seal
  • Verified
    Supplier
  • Credit
    Check
  • Capability
    Assessment

HD Series Electromagnetic Overload Protector Hydromagnetic Hydraulic Magnetic Circuit Breaker 32V 48V 60V 80V DC

Country/Region china
City & Province dongguan guangdong
Categories Battery Chargers
InquireNow

Product Details

 

HD Series Electromagnetic Overload Protector Hydromagnetic Hydraulic Magnetic Circuit Breaker 32V 48V 60V 80V DC

 

 

Hydraulic Magnetic Circuit Breaker

 

HD-30 and HD-50 are a new generation of circuit breakers for small and precision equipment, with advanced and reasonable structure, using hydraulic electromagnetic structure, mainly composed of operating mechanism, contact, decoupling mechanism, etc.


It has the characteristics of strong impact resistance, high flame retardancy, etc. It is a current-limiting high-sensitivity miniature circuit breaker with double protection of overcurrent and short circuit. The circuit equipment protector is a fully sealed structure, adopts copper contact, longitudinal magnetic field structure, and is equipped with the latest designed permanent magnet and spring energy storage operating mechanism. It has the characteristics of simple structure and reliable operation.

 

 

 

 

 

 

Tripping Principle Figure of Hydraulic Magnetic Circuit Breaker

 

 

 

Application of Hydraulic Magnetic Circuit Breaker

 

HD series hydraulic electromagnetic circuit breakers are suitable for AC 50/60HZ, rated voltage 250V and rated current 0.5-100A electrical system, used as the on-off operation of lines or equipment, and can be used to protect lines and motors from overload and short-circuit. Particularly suitable for use in occasions with impact or vibration, and also suitable for use in gasoline generator sets.

 

Computers and their peripherals
Industrial automation equipment
Telecommunications equipment
Communication equipment system
UPS uninterruptible power supply equipment
Railway locomotives
Boat
Elevator and other control systems
Mobile power equipment

 

The circuit breaker meets the requirements of GB17701-1999, C22.2 and IEC60934: 2000 standards; and has passed ROHS certification and CE certification.

 

 

Working and Installation Conditions of Hydraulic Magnetic Circuit Breaker

 

1. Ambient air temperature: the upper limit is +85℃, and the lower limit is -40℃.
2. The altitude does not exceed 2000 meters.
3. Temperature: The relative humidity of the air at the location where the circuit breaker is installed and used does not exceed 50% at a temperature of +85°C, the average minimum temperature of the wettest month does not exceed 25°C, and the average maximum relative humidity of the month does not exceed 90%.
4. The circuit breaker can be installed in places with significant impact and vibration.
5. When the circuit breaker is installed, the inclination of the vertical plane shall not exceed 5º
6. The circuit breaker should be installed in a place where there is no explosive dangerous medium, and there is no gas and dust (including conductive dust) that can corrode metals and damage the insulation.
7. The circuit breaker should be installed in a place where there is no erosion by snow or rain.
8. The installation category of the circuit breaker is Class III.
9. The pollution degree of the circuit breaker is level 3.

 

 

Main Technical Parameters of Hydraulic Magnetic Circuit Breaker

 

ModelHD-30HD-50HD-25
Rated current1A-50A1A-100A1A-30A
Rated voltage50/ 60Hz AC250V50/ 60Hz AC250V50/ 60Hz AC250V
Poles1P 2P3P4P1P 2P3P4P 2P
ConnectionBolt, PlugBoltPlug
InstallationFont mountingFont mountingFont mounting

 

 

Operation Characteristics of An Over-Current Release of Hydraulic Magnetic Circuit Breaker

 

1. Operation Characteristics

Trip currentOperating time(s)
 1In1.25 In2 In4 In6 In
ANon-action2~400.5~50.2~0.80.04~0.3
BNon-action10~900.8~80.4~20.08~1
CNon-action20~1802~100.8~30.1~1.5

 

2.Tripping Characteristic Curve

 

 

Outline & Installation Dimensions(mm) of Hydraulic Magnetic Circuit Breaker

 
 

Contact Details:

Andy Wu

Email: andy@tianrui-fuse.com.cn

MP/Whatsapp: +86 13532772961

Wechat: HFeng0805

Skype: andywutechrich

QQ: 969828363

 
 

Hot Products

Auto Part Car Yacht Manual Reset Over Current Overload Protector Motor Protection Circuit Breaker * ...
E96 Marine Boat Panel Mount Overload Protector Manual Reset Waterproof Circuit Breaker Single Pole ...
E94 25A to 200A Overload Protector Panel Mount Automatic Reset DC Circuit Breaker Specifications ...
J Series 1P 2P 3P 4P Screw Terminal Current Magnetic Mini Hydraulic Miniature 100A Circuit Breaker ...
HD Series Electromagnetic Overload Protector Hydromagnetic Hydraulic Magnetic Circuit Breaker 32V ...
DC Power Hexagon Rhombus Panel Mounted Auto Automatic Reset Circuit Breaker for Boat * Single pole, ...