Home Companies YUEQING FEEO ELECTRIC CO.,LTD

SPD Modular AC Surge Protector 40KA Rail 35mm Installation

YUEQING FEEO ELECTRIC CO.,LTD
Active Member

Contact Us

[China] country

Address: Keaisi Road, Xiangyang Industrial zone , Yueqing, Zhejiang,China.

Contact name:Terence

Inquir Now

YUEQING FEEO ELECTRIC CO.,LTD

SPD Modular AC Surge Protector 40KA Rail 35mm Installation

Country/Region china
City & Province zhejiang
Categories Other Security & Protection Products
InquireNow

Product Details

surge voltage protection, lightning protection over voltage protection

 

 

 

Product Description
 
lightning absorber Application:
FSP-A series surge protection device (in short SPD,alias:surge suppressor surge arrester)is
suitable for TN-S, TN-C-S, TT, IT etc, power supply system of AC 50/60Hz,<380V, installed on the
joint of LPZ1 or LPZ2 and LPZ3. It's designed according to IEC61643-1, GB18802.1, it adopts
35mm standard rail, there is a failure release mounted on the module of surge protection device,
When the SPD fails in breakdown for over heat and over-current, the failure rlease will help electric
equipments separate from the power supply system and give the indication signal, green means
normal, red means abnormal, it also could be replaced for the module when has operating voltage.
lightning absorber Product Features:
1. Inside over-current and over-heat protection, temperature control open circuit.
2. Module design, convenient installation, could be replaced online.
3. Time of response <25ns
4. The color of visible window shows operating status, green means normal, red means abnormal
lightning absorber Technical Date:
Technical ParametersFSP-A
Rated Operating Voltage Un(V~)380V/220V
Maximum Continuous Operating Voltage Uc(V~)275V320V385V385V385V420V
Voltage protection Level Up(V~)kV≤1.0≤1.2≤1.8≤2.0≤2.2≤2.8
Nominal Discharge Current ln (8/20s)kA51020304060
Maximum Discharge Current lmax(8/20s)kA1020406080100
Response Time (ns)<25
Test StandardIEC61643.1, GB18802.1
Operating Environment(centigrade)-40 ~+85℃
Max Connection Line35mm2 hard wire/35mm2 strand wire copper line
Recommended Connection Line16mm2 hard wire/25mm2 strand wire copper line
InstallationStandard Rail 35mm
Material of Outer CoveringBurning-proof Nylon
 

 

1. Air-termination system
Metal objects and metal structures that are used to directly receive or bear lightning strikes, such as lightning rods, lightning belts (wires), lightning nets, etc.
2. Down conductor system
The metal conductor that connects the air-termination device to the grounding device.
3. Earth termination system
The sum of the grounding body and the connecting conductor of the grounding body.
4. Earth electrode
A metal conductor buried in the ground that directly contacts the ground. Also called ground electrode. Various metal components, metal facilities, metal pipes, metal equipment, etc. that are in direct contact with the earth can also be used as grounding bodies, which are called natural grounding bodies.
5. Earth conductor
From the grounding terminal of electrical equipment to the connecting wire or conductor of the grounding device, or from the metal object that needs equipotential bonding, the general grounding terminal, the grounding summary board, the general grounding bar, the equipotential bonding bar to the connecting wire or conductor of the grounding device.
6. Direct lightning flash
Lightning that directly strikes actual objects such as buildings, the ground or lightning protection devices.
7. Ground potential counterattack Back flashover
The lightning current passes through the grounding point or grounding system and causes the ground potential of the area to change. The ground potential counterattack will cause the potential of the grounding system to change, which may cause damage to electronic equipment and electrical equipment.
8. Lightning protection system (LPS)
Systems that reduce lightning damage to buildings and installations, including external and internal lightning protection systems.
8.1 External lightning protection system External lightning protection system
The lightning protection part of the exterior or body of a building (structure) usually consists of an air-termination device, a down conductor, and a grounding device to prevent direct lightning strikes.
8.2 Internal lightning protection system
The lightning protection part inside a building (structure) usually consists of an equipotential bonding system, a common grounding system, a shielding system, reasonable wiring, surge protectors, etc., which are mainly used to reduce and prevent lightning current from being caused in the protection space. The electromagnetic effect produced.

 

Trade Ability

Language Spoken
English
 
No. of Employees in Trade Department
6-10 People
Average Lead Time
15
Export License Registration NO
04250042
 
Total Annual Revenue
confidential
 
Total Export Revenue
confidential
 

Hot Products

Disconnector Switch For Combiner Box 1000V Isoating Switch disconnector The high-voltage disconnecto...
DC MCB MINIATURE CIRCUIT BREAKER FPV-63 1P2P3P4P FPV-63 DC MCB supplementary protectors are designed ...
FDS-32 1000 V 1-32 A DC Fuse 10*32 MM And Holder With CE&TUV certificates A fuse is an electrical ...
3p amps miniature circuit breaker Product Description FE7-63 MCB is used in lighting distribution ...
surge voltage protection, lightning protection over voltage protection Product Description lightning ...
IP66 3 phase 20A Feeo AC power waterproof isolator switch waterproof isolator switch Features: 1. ...