Home Companies Jingo International CO., LTD

Addressable intelligent fire alarm 2 wire systems control panel 396 addresses

Jingo International CO., LTD
Active Member

Contact Us

Address: 3/F, 8Bldg, guilin Industry Area,Baoan district,Shenzhen, China.

Phone: 86-755-36326302

Contact name:Mr. Sales

Inquir Now

Jingo International CO., LTD

Addressable intelligent fire alarm 2 wire systems control panel 396 addresses

City & Province Shenzhen Guangdong
InquireNow

Product Details

 

Addressable intelligent fire alarm 2 wire systems control panel 396 addresses

2LOOPS  and 396 addresses

 

Features and Options:

  • More than 64 panels could be connected in one network.(optional)
  • One panel could connect 2 to 24 loops.
  • One loop could connect 198 addressable devices include the detectors and modules.
  • SLC(Single Loop Circuit) operates up to 10,000 ft. (3,800 m) with twisted, unshielded D3.2mm2 wire or 3,000 ft (900 m) with untwisted, unshielded D1.0mm2 wire.
  • Powerful polling protocol for faster panel response time less than 4 seconds. And response time less than 5 seconds from one panel to another panel in the network.
  • 320X240 Color TFT LCD display. 
  • Software based on ARM9 processor.
  • Devices(detectors and modules) could be registered automatically. 
  • Each addressed devices could be have a name with up to 40 characters (including spaces).
  • More than 2000 cause and effect items could be used to active output modules by alarm,fault, supervision, feedback in flexible and simple syntax. 
  • History file with 5,000 event capacity.
  • Graphic PC monitor software can be connect to the panel by RS232 or MODBUS port(optional).
  • More than 500 users could be registered in different level and password.
  • The panel could be programmed by USB port to download or upload program data.
  • Fully programmable from local keypad or keyboard or local PC
  • The detector real time sampling data curve could be showing on the LCD.

Specifications

AC Power – Terminal DZ1 of Main Circuit Board 

  • 220 VAC, 50 Hz, 1.5 amps
  • Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation

Battery (Sealed Lead Acid Only) – Terminal DZ2 of Main Circuit Board 

  • Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 1.00 amp
  • Maximum Battery Size: 18 Amp Hour
  • Minimum Battery Size: 7 Amp Hour
  • (FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 18 Amp Hour up to 26 Amp Hour batteries, use additional Battery Box)

Resettable DC24V Power (24 VDC nominal) –

Terminal DZ3, Terminals 1 (+) & 2 (-) & 3 (+) & 4 (-) of Main Circuit Board 

  • Maximum ripple voltage: 10 mVRMS
  • Up to 1.5 amps is available for powering devices. 
  • Power-limited circuit, nonsupervised

Nonresettable DC24V Power (24 VDC Nominal) –

Terminal DZ3, Terminals 5 (+) & 6 (-)

  • Maximum ripple voltage: 10mVRMS
  • Total DC current available from each output is up to 1.5 amps
  • Power-limited circuit, nonsupervised

Four Programmable Output Relay – 

Terminal DZ4 & DZ5 of Main Circuit Board 

  • Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
  • Each relay output can be set to Normal Close(NC) or Normal Open(NO) by the jump below the terminals.

Parts inside the panel:

Addressable fire alarm system architecture:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot Products

Addressable intelligent fire alarm systems coder Detector and module address programmer Battery ...
Addressable intelligent fire alarm 2 wire systems control panel 396 addresses 2LOOPS and 396 ...