Product Details

VS1(ZN63A)-12 Indoor AC High Voltage Vacuum Circuit Breaker

NINGBO TIANAN (GROUP) CO., LTD.

 

The structure of vacuum arc-extinguish room

Vacuum arc-extinguish room is the core parts from circuit breaker to support, connect and break current energy. It has sufficient arc-extinguish function and high operation duration.

  • Insulation enclosure (1) of arc-extinguish room is made up of high intensity alumina ceramics material, both ends shall be welded stainless steel cover (6) and it will be formed into sealed cavity.
  • Inner layer of arc-extinguish room is metal shied cover(5) which metal moist caused by arc can be compounded or condensed on the metal shied cover in short time during terminal making & breaking, insulation media intensity of inner arc-extinguish room will be recover. Meantime, shied cover can protect ceramics enclosure from hurt of metal splashing.
  • Retracted stainless steel accordion pipe (4) is the important part of arc-extinguish room that moving terminal (3) can move in the fully-closed arc-extinguish room. Sealing function and long duration of accordion pipe is one of the main factors which decided the mechanical duration of vacuum arc-extinguish room.
  • Terminal is the heart of vacuum arc-extinguish room, adopt chromium-copper, advanced smelt technology can ensure the breaking function and electric duration of vacuum circuit breaker, and decrease the operation over-voltage level.

 

The main parameter of 24KV circuit breaker

 

Rated voltage24kV
Rated frequency50Hz
Rated lighting impulse withstand voltage125kV
Rated 1 min power frequency withstand voltage65kV
Rated operation sequenceO-0.3s-CO-180s-CO
Rated current (A)630,12501250,1600,2000,2500
Rated short circuit breaking current (r.m.s, kA)20/2531.5
Rated short circuit making current (peak value, kA)50/6380
Rated short time withstand current/short circuit continuous time (kA/s)20,25/431.5/4
Rated peak value withstand current (kA)50/6380
Breaking times of rated short circuit(times)30
Mechanical duration (times)20000
Weight (kg)Fixed type≤250
Truck type≤350
NameUnitData
Distance of contact terminalmm12±1
Over-travel4±1
Three-phase opening & closing asynchronousms≤2
Tripping time of closing contact terminalms≤2
Closing & opening timeOpeningms≤50
Closing≤70
Average opening speed(after opening 6mm)m/s1.4±0.3
Average closing speed(after closing 6mm)0.8±0.2

 

Overview

The circuit breaker is identified by some national standards and international relative standards, such as GB1984,GB/T11022,DL/T403 and IEC62271, etc. It has reliable lockage, used as truck department or fixed installation department.

VT19-24indoor HV vacuum circuit breaker is used in the mining company ,power factory and substation,which is widely used in the rated current or multiple breaking short circuit current.

Hot Products

Compact Substation 11kv Compact Substation Power Transformer Box Electricity Substation ZGS-Z.G-2750...
XGN68-12(F), XGN68-12(F.R), XGN68-12(Z) Box Type (Indoor) AC Metal-clad Switchgear is the latest HV ...
1.General Introduction KYN28-12 withdrawable metal-clad switchgear (hereinatter called KYN28 ...
VS1(ZN63A)-12 Indoor AC High Voltage Vacuum Circuit Breaker NINGBO TIANAN (GROUP) CO., LTD. The ...
1. General introduction XGTD8-12 indoor environmental gas insulated metal-clad switchgear ...