[China]
Trade Verify
Address: No. 15, Zhenxing North Road, Fengjing Industrial Park, Huayi District, Xi'an City, Shaanxi Province
Contact name:liu
Xi'an Wuhuan Special Fuse Co., Ltd., |
Verified Suppliers
|
|
Bay-O-Net Tap Changer Switch Fuse for Oil Transformer Prnt4-24/31.5
PRNT4-15.5, PRNT4-24, PRNT4-40.5 series of high-voltage fuses for
overload protection of oil-immersed transformers are suitable for
use in power systems with AC rated frequency of 50Hz and rated
voltage of 15.5kV, 24kV and 40.5 kV respectively. As the overload
protection protection element for power transformer and other power
equipment, the fuse is installed in the transformer oil of American
type box transformer or other box transformer, and can be co-boxed
with transformer and load switch. The oil-immersed transformer
overload protection high-voltage fuse can not be used alone, can be
connected in series with the transformer backup protection
high-voltage current-limiting fuse to form a full range of
high-voltage current-limiting fuse. When the overload current
exceeds the specified value for a certain period of time, the
circuit is opened by the overload high-voltage fuse. When the
short-circuit current passes through the fuse, the short-circuit
current is opened by the backup high-voltage current-limiting fuse.
The product can be widely used in the distribution protection of
wind power generation, solar power generation, tide stream power
generation and other equipment.
This product consists of two parts: overload protection fuse and
plug-in bracket.
1. Model and meaning :2. This product is composed of overload protection fuse and fuse
holder.
2.1 Basic engineering data:
Model number | Rating current of fusible core (A) | Service enviornment | Rating breaking current (KA) |
PRNT4-15.5 PRNT4-24 PRNT4-40.5 | 5, 6.3, 10 , 16,
25, 40, 50, 63 100, 140 | in transformer oil | 2.5 |
Note:Dual fuse maximum 63A
2.2 See picture 1 for the size and installation of the overload
protection fuse Picture 1,XRNT4-15.5 High voltage fuses for overload protection of
oil immersed transformer .
2.3 See picture 2 and picture 3 for the dimension and
installation of the plug-in fuse holder3. Installation steps of fuse wire:
4. Time-current characteristic curve of bay-o-net fuse as below :
Transformer capacity (KVA) | 12KV power system | 24KV power system | 40.5KV power system | |||
overload fuse | Backup current limiting fuse | overload fuse | Backup current limiting fuse | overload fuse | Backup current limiting fuse | |
100 | PRNT4-15.5/10 | XRNT4-15.5/31.5 | PRNT4-24/6.3 | XRNT4-24/16 | PRNT4-40.5/5 | XRNT4-40.5/10 |
200 | PRNT4-15.5/16 | XRNT4-15.5/40 | PRNT4-24/10 | XRNT4-24/20 | PRNT4-40.5/8 | XRNT4-40.5/16 |
315 | PRNT4-15.5/25 | XRNT4-15.5/50 | PRNT4-24/16 | XRNT4-24/32 | PRNT4-40.5/10 | XRNT4-40.5/20 |
400 | PRNT4-15.5/32 | XRNT4-15.5/63 | PRNT4-24/20 | XRNT4-24/40 | PRNT4-40.5/16 | XRNT4-40.5/31.5 |
500 | PRNT4-15.5/40 | XRNT4-15.5/80 | PRNT4-24/25 | XRNT4-24/50 | PRNT4-40.5/20 | XRNT4-40.5/40 |
630 | PRNT4-15.5/50 | XRNT4-15.5/100 | PRNT4-24/31.5 | XRNT4-24/63 | PRNT4-40.5/25 | XRNT4-40.5/50 |
800 | PRNT4-15.5/65 | XRNT4-15.5/125 | PRNT4-24/40 | XRNT4-24/80 | PRNT4-40.5/25 | XRNT4-40.5/50 |
1000 | PRNT4-15.5/80 | XRNT4-15.5/150 | PRNT4-24/50 | XRNT4-24/100 | PRNT4-40.5/31.5 | XRNT4-40.5/63 |
1250 | PRNT4-15.5/100 | XRNT4-15.5/175 | PRNT4-24/65 | XRNT4-24/125 | PRNT4-40.5/31.5 | XRNT4-40.5/63 |
1600 | PRNT4-15.5/140 | XRNT4-15.5/200 | PRNT4-24/80 | XRNT4-24/150 | PRNT4-40.5/40 | XRNT4-40.5/80 |
2000 | XRNT4-15.5/250 | PRNT4-24/100 | XRNT4-24/200 | PRNT4-40.5/50 | XRNT4-40.5/125 | |
250 | PRNT4-40.5/65 | SRNT4-40.5/125 |
Model and meaning
Xi 'an Wuhuan Special Fuse Co., Ltd. is a high-technology
manufacturer company established by Wuhuan Electric Group in Xi
'an, Shaanxi Province, China's high voltage electric production
base in 2000. It mainly engaged in the development,
design, manufacture, sales and service of fuses and other high
voltage appliances. The main products of the company are
high-voltage current limiting fuses, which are used in indoor
50HZ/60HZ power systems with rated voltage of 3.6-40.5KV. As
American power transformer, Europe type power transformer, high
voltage motor, voltage transformer, power capacitors and other
electric equipment overload and short circuit protection, and in
other appliances such as: load switch, vacuum contactor etc,
protection circuit and complete sets of electrical equipment from
damage by excessive overload current and short circuit current. The
company has high-quality technical personnel, professional fuse
manufacturing and testing equipment and advanced modern enterprise
management concept, its product categories, production scale and
sales revenue are growing at a high speed. Wuhuan Company
implements ISO9001:2000 quality system standard, uses MCAD
development and design, with the help of Intuitive ERP and advanced
testing equipment to ensure the reliability of production and high
quality products. All the products have passed the type test of the
national high voltage electrical apparatus quality supervison and
inspection center ,and are in line with the national GB/T15166.2
standard and IEC60282 standard of the International
Electrotechnical Commission.