BS7629-1 Standard Fire Performance Cable Enhanced Fire Resistant Cable

 

 

 

APPLICATION

Hard Skin Enhanced Fire Resistant Cables for use primarily in fire detection, fire alarm, voice alarm, and emergency lighting circuits. These cables are designed to continue to operate for a period of time in a fire situation. ‘Enhanced grade’ fire resistance is recommended for systems, in particular building types, in which cables might need to operate correctly during a fire for periods in excess of those normally required for single phase evacuation of a building.

 

STANDARDS

BS 5839-1:2013 Clause 26.2e, BS EN 50200:2015 (PH 30 - PH 60 - PH 120), BS 6387:2013, BS 7629-1, IEC 60331

BS 6387 (cat. C-W-Z), BS EN 50200 (class PH120), BS EN 50200, BS 8434-2 (120 min), BS EN 60332-1-2,

BS EN 60332-3-24 cat. C, BS EN 60754-1, BS EN 60754-2, BS EN 61034-2, BS 5266-1, BS 8519

 

Voltage Rating300/500 volts
DescriptionFiretec Standard cable is suitable for fire alarm systems, emergency lighting and BS 5839-8 voice alarm systems. It meets the standard grade of BS 5839 26.2d & Category 1 Control as defined by BS8519.
ConstructionSolid or stranded plain annealed copper conductors. Tinned annealed copper full size CPC. Aluminium/polyester laminated tape screen. LSZH insulation and outer sheath.
Operating Temperature-10degC to +90degC
Minimum Bending Radius6 x overall diameter
Core Identification2 core Bn, Be
3 core Bn, Bk, Gy
4 core Bn, Bk, Gy, Be
Lengths100/500m
Special lengths available on request.
Sheath ColourRed or White. Other colours available.
Manufacturing StandardBS 7629-1
Code of Practice/
Guide to Use
BS 5839-1 Clause 26.2d Standard
BS5839-8
BS 5266
BS 8519 Category 1 Control
Fire TestsBS7629-1 STANDARD 60
BS EN 50200 PH30, PH60, PH120
BS 6387 C W & Z
Emissions and
Flame Propagation
BS EN 60754 (BS EN 50267) Acid Gas Emission
BS EN 61034-2 (BS EN 50268) Smoke Emission
BS EN 60332-1-2 (BS EN 50265,50266) Flame Propagation

 

DIMENSIONS

Class 1 Solid Plain Conductor

UNI-Cables
PART NO.
NO. OF CORESNOMINAL CROSS SECTIONAL AREAEARTH WIRE CONSTRUCTIONNOMINAL OUTER DIAMETERNOMINAL WEIGHT
mm2n° /mmmmkg/km
UNIFR02015/ENH21.51/1.188.8105
UNIFR02025/ENH22.51/1.7510.2150
UNIFR03015/ENH31.51/1.389.3130
UNIFR03025/ENH32.51/1.7510.8190
UNIFR04015/ENH41.51/1.3810.3165
UNIFR04025/ENH42.51/1.3812240

 

Class 2 Stranded Plain Conductor

UNI-Cables
PART NO.
NO. OF CORESNOMINAL CROSS SECTIONAL AREAEARTH WIRE CONSTRUCTIONNOMINAL OUTER DIAMETERNOMINAL WEIGHT
mm2n° /mmmmkg/km
UNIFR02040/ENH247/0.8512.2220
UNIFR03040/ENH347/0.8513280
UNIFR04040/ENH447/0.8514.4350

 

 

ELECTRICAL CHARACTERISTICS

NOMINAL CROSS
SECTIONAL AREA
mm2
CONDUCTOR RESISTANCE AT 20ºC
Ω/km
INSULATION RESISTANCE AT 20ºC
MΩXkm
NOMINAL CAPACITANCE
pF/m
Core / CoreCore / Screen
118.130095160
1.512.1300110170
2.57.41300120200
44.61300150250

 

 

CURRENT CARRYING CAPACITY

Clipped Direct

NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT RATING
2 Core
Amps
3 and 4 Core
Amps
11917
1.52422
2.53330
44540

In Conduit or in Cable Tray

NOMINAL CROSS SECTIONAL AREA
mm2
CURRENT RATING
2 Core
Amps
3 and 4 Core
Amps
11715
1.52219.5
2.53026
44035

 

 

 

VOLTAGE DROP

Clipped Direct

NOMINAL CROSS SECTIONAL AREA
mm2
VOLTAGE DROP
2 Core
mV/A/m
3 and 4 Core
mV/A/m
14539
1.53026
2.51815
41110

In Conduit or in Cable Tray

NOMINAL CROSS SECTIONAL AREA
mm2
VOLTAGE DROP
2 Core
mV/A/m
3 and 4 Core
mV/A/m
14539
1.53026
2.51815
41110

Hot Products

Type PV Red Color Single Conductor 2000V Aluminum Alloy 8030 Conductor XLPE Insulation CONSTRUCTION: ...
4/C AL 600V XLPE XHHW-2 AIA PVC Power Cable Type MC Building Cable CONSTRUCTION: 1. Conductor: Class ...
YJHLV Aluminum Alloy Cable AA8030 Conductor XLPE Insulated Multicore Power Cable APPLICATIONS YJHLV ...
BS7846 CU/XLPE/SWA/PVC Fire Performance Cable LSZH Fire Resistance Cable APPLICATION FR-RES Power ...
BS7629-1 Standard Fire Performance Cable Enhanced Fire Resistant Cable APPLICATION Hard Skin ...
Multi Core Fire Resistance Cable Unarmoured Cu/MICA Overall Screened Fire Cable APPLICATION These ...