DJSF1352-RN/D-P1 Energy Meter

Country/Region china
City & Province jiangsu
Categories Measuring & Gauging Tools
InquireNow

Product Details

General


DJSF1352-RN rail-mounted DC power meter with double DC input channels, designed for telecommunications base stations, DC charging piles, solar photovoltaic and other applications, this series of meters can measure the voltage, current, power and forward and reverse energy and so on in the DC system.

Features


 

Dual Independent DC Circuits Monitoring

● For Twin EV Charger&Battery

● Voltage Input:DC 0~1000V

● Current Input (by Shunt): 0~75mV

● Current Input (by Hall Sensor): 0~5V, 0~10V, 0~20mA, 4~20mA

 

Built-in Bipolar Power Source

● Power Supply for Hall Effect CT

● Range: DC -12V ~ DC +12V 

 

Optional Dual RS485 Communication

● Protocol: MODBUS-RTU

● 1 RS485 (standard)

 

DO/DI Function

● 2 DO (2A/30V DC; 2A/250V AC)

● 2 DI (dry contact)

 

Keypads HMI for Programming

● Parameter Display Setting

● Communication

 

Technical parameter


Technical parameters 

Indicators

InputNominal valueVoltage input rangeCurrent input

DC 0-1000V

See the physical wiring diagram

Shunt:0-75mV;

Hall sensor:0-20mA,4-20mA,0-5V,0-10V and so on.

OverloadOverload

1.2 times rated (continuous); 2 times rated/1 second;

Power consumptionPower consumptionVoltage: ≤0.2VA, current ≤0.1VA
Accuracy classClass 1
FunctionDisplay8-bit segment LCD screen (LCD)
Communication Interface

RS485, infrared

Communication protocolModbus-RTU,DL/T 645-2007
SwitchSwitch output2 Relay outputs, 2A/30VDC or 2A/250VA
Switch input2 dry contact inputs
Pulse outputA second pulse output, a energy pulse output

See the SYS->PLUS display in the meter menu setting

For example: The meter displays 100, which is 100imp/kWH

Power SupplyVoltage rangeAC/DC 85-265V or DC24V(±10%) or DC48V(±10%)
Power consumption≤ 3W
Power frequency withstand voltagePower supply // Voltage input // Current input // Relay output and switch input // Communication interface / / Pulse output 3kV/1minPower supply // Relay output // Voltage input // Current input 3kV/1minPulse output // Communication interface // Switch input 2kV/1min
Insulation resistance

≥ 40M Ω

Average barrier-free working hours

≥50000h

Environment

Temperature

Normal operating temperature: -25 °C ~ +65 °C;

Limit working temperature: -40 °C ~ +70 °C;

Storage temperature: -40℃~+80℃

Humidity

≤93%RH, no condensation, no corrosive gas

Altitude≤2500m

 

Wiring


with shunt

with sensor

 

Certification


 

Hot Products

General DJSF1352-RN rail-mounted DC power meter with double DC input channels, designed for ...
AMC16-DETT 48V energy meter AMC16-DETT DC power meter is mainly designed for measurement of electric ...
General ATE series temperature measuring sensor has been developed in compliance with Specification ...
General ATC600 energy meter can be used in 3~35kV indoor switch cabinets, including central cabinets...
General adw300 energy meters allow the acquisition of energy meter readings and transmit data over ...
AGF-AE-D/200 Electricity Meter Features ■Standard 35mm guide rail installation; ■Suitable for a ...