Home Companies ShanDong HangKang Medical Equipment Co.,Ltd.

LK-YAN8300A /LK-YAN8600A/LK-YAN7200A Anesthesia Machine

ShanDong HangKang Medical Equipment Co.,Ltd.
Active Member

Contact Us

[China] country

Address: A703-03, Jinquan Dasha, 56 Jiefang DongLu, Lixia district , Jinan City , Shandong province 

Contact name:Aana Yue

Inquir Now

ShanDong HangKang Medical Equipment Co.,Ltd.

LK-YAN8300A /LK-YAN8600A/LK-YAN7200A Anesthesia Machine

Country/Region china
City & Province jinan shandong
Categories Solar Chargers
InquireNow

Product Details

1.PCV and SIMV+PS modes ensure flexibility in ventilation, suitable for both pediatric and adult operation
2. Flowmeter with backlight, suitable for endoscopy surgery etc.
3.Breathing system warmer for avoid condensation build-up during low-flow anesthesia
4. Enhances usability with auxiliary oxygen, suction, auxiliary power source, monitor arm, infusion pump etc.
5. Optional functions monitoring O 2 , CO 2 and anesthetic gas
6.With CE certificate, meets EU clinical requirement
Dimensions(W×H×D)
704mm × 1403mm × 750mm
Weight
115kg (including trolley base and 2 vaporizers without cylinder
Operation Temperature
+10~+40°C
Operation Humidity
≤80% (noncondensing)
Battery
24V DC, minimum 120 min
Patient Types
Adult, Pediatric

 

 
Technical Specifications:
 

Gas requirement: Medical oxygen and nitrous oxide with a pressure ranging from 280~600kpa

safety valve <12.5 kPa

Respiratory Rate 1~99 bpm

gas concentration output 21% ~ 100% adjustable

Maximum Minute ventilation ≥18L / min, permissible deviation: ±20 %

Breathing Mode A/C, SIPPV,IPPV,SIMV,PSIMV,CPAP,PCV, PEEP,SIGN,VCV, SPONT, MANUAL

Ventilator compliance ≤30 Ml/kPa

PEEP: 0~1.0KPa

Ptr: ,-1.0~1.0 kPa

IMV frequency: 1 ~ 12 times/min, permissible deviation: ±15%.

I/E Ratio: 4:1~1:4

Tidal Volume range 0~2000ml

Inspiratory Plateau: 0~1s

Maximum Safety Pressure ≤ 6.0kPa

Sigh: one deep breath per 80 controlled respirations, the inspiration time is 1.5 times of the setting point and the permissible error is -10% or 15%.

Pressure limit range: 1.0~ 6.0kPa

Airway pressure alarm: Audible and visual and with yellow and red color indicating upper alarm: 0.9 kPa ~ 5.4 kPa

lower: 0.5kPa

Ventilation Volume alarm: ≥ 18L/ MIN

Power Supply Alarm "Ac/dc power supply are after failing to send out alarm immediately

Alarm Time: keep >120s"

The airway pressure continues to be higher than 15 hPa ±1 hPa for 15s±1s, then the machine will raise an audible alarm, the pressure will be displayed in red and the continuous high pressure red alarm wording is displayed on the screen of the anesthetic respirator.

 
Ambient temperature10 ~ 40oC
Relative humidityno higher than 80 %
Atmospheric pressure860 hPa ~ 1060 hPa
Power requirement100-120 Vac, 50/60 Hz;
Air source requirementMedical oxygen and laughing gas with a rated pressure ranging from 0.3 to 0.5MPa.
Attentionthe AC power supply used for the anesthesia machine must be well grounded.
Attentionthe anesthesia machine used must be equipped with a carbon dioxide monitor complying with ISO 9918:1993, an oxygen monitor complying with ISO 7767:1997 and an expiratory gas volume monitor complying with 51.101.4.2 of Medical Electrical Equipment
Part IISpecial Requirements for Safety and Basic Performance of Anesthesia System.

Hot Products

1.PCV and SIMV+PS modes ensure flexibility in ventilation, suitable for both pediatric and adult ...
ENT endoscope camera system OM-822A Full HD endoscope camera System OM-822C 3 Chips FULL HD camera ...
Medical Equipment High Quality Portable 3D 4D color doppler ultrasound MSLCU64 for Gynaecology A ...
Multi-parameter patient monitor ,ETCO2 available ,12 inch portable patient monitor Company ...
-86 degree ultra low temperature laboratory freezer 1.Features Optimized cascade refrigeration ...
Product Application   Medical Refrigerators are special designed for the Chemical reagent; Vaccine; ...