Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

120mm Resin Casting Zero Sequence Current Transformer Split Core Protection

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

120mm Resin Casting Zero Sequence Current Transformer Split Core Protection

Country/Region china
City & Province beijing beijing
InquireNow

Product Details

 

 

LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20

 

 

GFUVE LZCK2500-10 is a zero sequence current transformer, can used wildly,the accuracy up to 10P5 and 10P10 5P20.

The protection current transformer is used to reduce the currents in power systems, producing proportional currents in the unit’s secondary windings that remain isolated from the main circuit. The replica current is then used as an input to a protective relay, which can then automatically isolate part of the power circuit should it experience a fault.

 

Protection Current Transformers are designed to measure the actual currents in power systems and to produce proportional currents in their secondary windings which are isolated from the main power circuit.

 

protection cts are used for protection against over current or faulty current, their secondary is

thusconnected to the protection relays and the to the tripping coil. there may be series or shunt

tripmechanism, thus the burden(VA) of protection ct is more as compared to metering cts.

 

The classification of protection current transformers follows the following simple formula: "10 P10" Manufacturers of protection devices will normally specify the classification for the

protection current transformer intended to operate the particular protection device concerned.

 

This is required for protection CT, because the fault current is high and the CT should be able tosense the high fault current accurately to protect the system. The common numbers are 10, 15, 20 and 30. Class PS: PS is for 'Protection Special'. This class of CT's are used for special

Protection such as differential protection, distance

 

Parameters

Technical parameters 
StandardsIEC60044; IEC 61869; ANSI/IEEE C57.13
Rated primary current50-600A
Rated load≤30VA
Rated frequency50Hz or 60Hz
Rated secondary current5A or 1A
Rated short-time thermal current40kA, 1S
Rated dynamic current63kA
Rated insulation level12/42/75KV
FS≤10
Mechanical parameters 
MaterialEpoxy resin
Weight (kg)18
Operating conditions 
Operating temperature-10°C to +55°C
Daily average temp<+40°C
Storage temperature-40°C to +70°C
Altitude<1000 meters
ConditionNo existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current.

 

Technical Data

 

Rated Current RatioAccuracy ClassRated Output(VA)
50/110P52
60/12
75/12
100/12
150/110P102.5
200-300/12.5
400-600/12.5
50/510P55
75/5 
100/510
150-300/510P1020
350-600/530

 

Order information

 

If you want to learn more information,please feel free to contact us. 

Hot Products

LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...
S120 1200A 1MV/A AND 1MA/A OUTPUT AC CURRENT CLAMP ON CT Description The S120 is a high performance ...
Q125B High Accuracy Current Clamp On Measuring Instrument Description The Q125B is a high performanc...
HQ46 CABLE TYPE 500A MV OUTPUT AC CLAMP ON CURRENT PROBE Description The HQ46 AC Current Probe is ...
HQ15 HIGH-VALUE VOLTAGE OUTPUT AC CURRENT CLAMP SENSOR Description The HQ15 AC Current Probe is ...
FEATURES AND TECHNICAL PARAMETERS Calibrate three phase, single phase, active or reactive meter ...