Home Companies Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

GF106T Smart Electrical Test Equipment CT PT Testing With Current Injection Function

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
Active Member

Contact Us

[China] country

Address: Oriental HuaRui A, No. 150 Guanzhuang Road, Chaoyang District, Beijing, 100024, China

Contact name:Andy

Inquir Now

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

GF106T Smart Electrical Test Equipment CT PT Testing With Current Injection Function

Country/Region china
City & Province beijing beijing
Categories Other Electric Power Tools
InquireNow

Product Details

 

GF106T Smart Electronic Test Equipment for CT PT Testing with Current Injection function

It is mainly used for field testing of P class CT and PT. The test items mainly include excitation characteristic, transformation ratio, polarity, degauss, 5% and 10% error curves, secondary circuit check, withstand test of power frequency alternating current and secondary load. Adopting LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.

Portable CT PT analyzer brings a lot of convinent for engieers to test CT on feild. Easy opearte and bring.

GFUVE GF106T is the basic model of CT PT analyzer, which used generate large curren and voltage for testing Ct and PT. This Model is economy, working stable .

 

MAIN FUNCTIONS

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Withstand test of power frequency alternating current
5. Current Injecting5. Degauss
6. Degauss6. Calculation of knee point value
7. Withstand test of power frequency alternating current7. Actual secondary load test 
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test 
10. Resistance test 

PARAMETERS

Electrical parameters
Accuracy0.2%, 0.5%
Power supplyAC 220V±10% or AC 110V±10%, 50/60Hz
Excitation voltage output0-2500Vrms,
Excitation current output0-5Arms (20A peak-value)
Large current output0-1000A
Electrical parameters - continued
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurementRange0.1-300Ω
Accuracy≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurementRange5VA-1000VA
Accuracy≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurementAccuracy±4min
Resolution0.01min
CT ratio error measurementRange≤25000A/5A(5000A/1A)
Accuracy≤0.5%
PT ratio error measurementRange1-500KV
Accuracy≤0.5%
Standards 
Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standardsGB 4793.1-2007
EMCEMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm)400 x 250 x 250
Weight (kg)≤22
Environmental conditions 
Relative humidity90RH%
Operating temperature-10°C to +40°C
Altitude≤1000m

 

 

Hot Products

LZZT620-10 resin cast Three phase bushing type Zero Sequence Current Transformer for protection ...
LZZT943-10 resin cast Three phase Zero Sequence Current Transformer for Ring cabinet and inflatable ...
150mm diameter 2000A/1A 5P20 Cast Resin Zero Sequence Current Transformer with IEC 61869-2 LZCK2501 ...
LZCG530-10 Protection relay device using 5P20 50/1A Zero Sequence Current Transformer Zero Sequence ...
LZCG530-10 Zero Phase Current Transformer, Ring net cabinet 5P10 Ratio 100A / 1A Zero Sequence ...
LZCK2500-10 120mm 50/5a Resin Casting Split core Protection Zero Sequence Current Transformer 5P20 ...