Qingdao Yilan Cable Co., Ltd. |
Verified Suppliers
|
|
3-Core Underground Steel Tape Armored XLPE Insulated Power Cable
Description of multi-core power cable:
1. Conductor: copper or aluminum.
2. Provide armored and non-armored power cables.
3. Rated voltage: 0.6 / 1kv 3.6 / 6kv 6 / 10kv 8.7 / 15kv 26 / 35kv
4. PVC or XLPE insulation.
5. Standards: IEC, BS, ASTM, NFC, AS, GOST, etc. Or other special
features according to customer requirements.
6. The maximum long-term working temperature of the PVC insulated
cable is 70°C, and the cross-linked polyethylene is 90°C.
7. The installation temperature of the cable should not be lower
than 0°C.
8. The maximum short-circuit temperature is: PVC does not exceed
160°C, XLPE 250°C, no more than 5 seconds
9. Cable with allowable bending radius: no less than 10 D times (D:
outer diameter of the cable)
Features and uses of XLPE insulated power cables:
The cross-linked polyethylene insulated power cable has the characteristics of high mechanical strength, strong environmental stress resistance, excellent electrical performance, and strong current resistance.
Chemical corrosion. In addition, the lightweight and simple product
is easy to use. This product is suitable for transmission and
distribution systems with a rated voltage of 0.6/1kv.
It has the main characteristics of fire-resistant cables. The
cables are not easy to catch fire or continue to burn within a
certain range. It is suitable for power stations, subways, tunnels,
high-rise buildings, and large-scale
Dense distributed cables in industrial and mining enterprises, oil
fields, coal mines and other places.
Executive standard:
GB/T 12706, IEC 60502 and related domestic and foreign standards,
such as BS, VDE, JIS, AEIC, etc.
Physical and Electrical Characteristics
No.cores x | Insulation | Sheath | Outer Ø | weight | Current ratings in air 30℃ | Current ratings buried 20℃ | |
cross-sec. | thickness | thickness | approx. | approx. | |||
Nominal | |||||||
Phase | Neutral | value | |||||
mm² | mm | mm | mm | mm | kg / km | A | A |
3×4+1×2.5 | 0.7 | 0.7 | 1.8 | 12.7 | 277 | 37 | 47 |
3×6+1×4 | 0.7 | 0.7 | 1.8 | 13.9 | 363 | 47 | 60 |
3×10+1×6 | 0.7 | 0.7 | 1.8 | 16.1 | 527 | 64 | 81 |
3×16+1×10 | 0.7 | 0.7 | 1.8 | 18.6 | 766 | 85 | 106 |
3×25+1×16 | 0.9 | 0.7 | 1.8 | 22.2 | 1140 | 113 | 137 |
3×35+1×16 | 0.9 | 0.7 | 1.8 | 24.6 | 1475 | 139 | 164 |
Application
Wiring for fire safety circuits, such as fire alarm systems in
high-rise buildings, emergency lighting and power supplies, public
address and emergency voice communication systems, control and
instrumentation services for industrial, commercial and residential
complexes.
Special functions on request:
•Oil resistance
• UV resistance
• Flame retardant cat. A, B, C
•Non-flame retardant
•termite
• Rodent
• Low smoke zero halogen