KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

1. General Of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

KYN61-40.5 Air Insulated Metal-clad Switchgear is suitable for application at three phases, 50Hz, 40.5kV power distribution system. This product has functions of protection, control and monitoring.

 

2. Service condition of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

a. Ambient temperature: +40 to -15℃

b. Elevation: no more than 10000m

c. Humidity:

Daily average relative humidity shall be not higher than 95%

Monthly average relative humidity shall be not higher than 90%

d. Earthquake: no more than 8 degree

Ambient air should be free of the obvious pollution of aggressive or flammable gases, or vapor, etc.

The usage of the product beyond of the environment for demanded technical conditions should be after the negotiation between the client and factory.

 

3. Type designation of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

4. Technical parameters and requirement of KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear

 

No.ItemUnitParameter
1Rated voltagekV40.5
Rated frequencyHz50
3Rated main busbar currentA1250, 1600, 2000
4Rated branch busbar currentA1250, 1600, 2000
5Rated insulation level1min power frequency withstand voltagekVPhase to phase, Phase to earthPrimary Insulation Distance
95115
Lightning impulse withstand voltage185215
1min power frequency withstand voltage of Auxiliary control circuitV2000
6Rated short circuit breaking current (effective value)kA25, 31.5
7Rated making current(peak time)kA63, 80
8Rated short time peak withstand currentkA63, 80
94 s’ short time withstand currentkA25, 31.5
10Rated voltage of auxiliary control circuitV≈110, ≈220
11Protection level Enclosure IP4X, Chamber IP2X
12Overall sizemm1200 or 1400x2800x2600

 

 

Hot Products

KYT1 (KYN61)-40.5 Metal-clad Draw-out AC Switchgear 1. General Of KYT1 (KYN61)-40.5 Metal-clad Draw...
Hight voltage Switch cabinet XGN65 (HXGT10)-40.5 type SF6 Ring Main Unit Main purpose and applicatio...
Description: KYN10-40.5 series AC metal-enclosed switchgear is the latest self-designed and ...
XGN49 SF6 Indoor High Voltage Switchgear – 2500A Gas Insulated Switchgear Product Description of ...
Indoor Gas Insulation Metal-Clad Switchgear / Air Insulated Switch Cabinet Overview of Indoor Gas ...
XGN49-40.5KV 1250A GIS SF6 High Voltage Switchgear With Cabinet Structure Overview of XGN49-40.5KV ...