Product Details

HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear

 

Brief introduction of HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear:

HXGT18(HXGN26)-24(L) Box type AC metal-clad Switchgear(RMU for shorts) is designed and developed by our company, which introduce into foreign advance technique and accord with national power supply requirement. After the type test and long trial operation check, the product performance index has reached IEC298and GB3906<3-35KV AC Metal-clad switchgear>, and meet the reliable fault prevention operation function of the two parts requirements, protection degree reached IP2X. This product features small bulk, light weight, easy operation, safety operation, easy maintenance, etc. It is a newly type of high voltage switchgear suitable for municipal power net improvement and reconstruction.

 

Application for HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear:

It is suitable for power transmission and distribution, AC, 50Hz, 10kV power supply net.

 

Type designation of HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear:

 

 

 

 

Technical parameter of HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear:

NameUnitDate
Rated voltagekV24
Rated frequencyHz50
Rated current of main busbarA630
Rated short time withstand current of main circuit,earth circuitkA/S25/2
Rated peak withstand current of main circuit,earth circuitkA63
Rated short circuit making current of main circuit,earth circuitkA63
Full capacity breaking times of load switchTimes100
Fuse breaking currentkA31.5 40
Mechanical enduranceTimes10000
1 min power frequency withstand votlage (r.m.s) phase to phase,phase to earth/isolating distancekV50/65
Lighting impulse withstand votlage (peak) phase to phase,phase to earth/isolating distancekV95/110
1min power frequency withstand voltage of secondary circuitkV2

 

Notes for ordering of HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear:

a. Product name, type, scheme code, quantity and delivery date

b. Name, type, specifications and quantity of inside components

 

 

 

c. Alignment diagram or layout diagram of RMU

d. Buyers indicate main busbar material, if not, as per factory specification

e. Secondary scheme diagram

f. Enclosure color, if not as per factory standard

Hot Products

Ring Main Unit Switchgear Air Insulated Switchgear, HXGN11-12 Product introduction of Ring Main Unit ...
VC-V12 AC Metal-clad Switchgear 1.Product Introduction The applicable standards for VC-V12 AC Metal...
HXGT18 (HXGN26)-24(L) Indoor AC HV Box Type Metal-clad Switchgear Brief introduction of HXGT18 ...
HXGT6 (XGN58)-12 SF6 Gas Filled Type RMU Switchgear General of HXGT6 (XGN58)-12 SF6 Gas Filled Type ...
12KV Box Type & Fixed Type AC RMU Indoor Switchgear Application Range of 12KV Box Type & Fixed Type ...
XGN58 (HXGT6A)-24 box type gas insulated metal-clad switchgear Overview of XGN58 (HXGT6A)-24 box ...